Operation
93
SIPART PS2 Manual
A5E00074631--06
The display of the positioner shows you the current potentiometer
setting in the top line and “NOINIT” flashes in the second line. You can
move the actuator with the decrement and increment key
. In order
to adapt the positioner to your actuator, you have to change to the
Configuration menu. See also chapter 3.6, page 72 “Commissioning”.
Output of alarms and position feedback is possible after successful init-
ialization.
To go to the Configuration menu, press the operation mode key
for
at least 5 seconds. In the Configuration menu you can adapt the
positioner individually to your actuator and start initialization. Only a few
parameters need to be set in the positioner prior to initialization. The
others are defaulted so that they do not normally need to be adjusted.
You can block the Configuration menu against manipulation by an
appropriately parameterized and activated digital input. Which
parameters you need to set and all other parameters are explained in
chapter 4.4, page 95 Parameters.
The configuration mode can be reported by outputting a
parameterizable fault message, a position feedback or output of limit
values A1 and A2 is not possible.
.
NOTE
If the electric power supply fails during configuration, the positioner
switches back to the first parameter after recovering the power supply,
values which have already been parameterized are retained. When
doing this, please note that the new value will only be saved when
leaving the configuration menu or when another parameter is selected.
Without a power failure you re-enter the configuration menu at the
point you exited it when you call the Configuration menu again.
P-manual mode
(ex-factory state)
Configuration and
initialization
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...