Operation
132
SIPART PS2 Manual
A5E00074631--06
Error
code
three-
level
Event
Parameter-
setting
Error message
disappears if...
Possible
causes
1
no
Remaining control
deviation
always active
... the control
deviation has
disappeared again.
Compressed air
missing, actuator
fault, valve fault
(e.g. blockage).
2
no
Device not in
automatic mode
47. FCT= nA
or = nAB
... the device is
switched to automatic
mode.
The device is
configured or is in
manual mode.
3
no
Binary input BE1
or BE2 active
47. FCT= nAB
and binary function
BIN1 or BIN2 at “on”
... the binary input is
no longer activated.
The contact
connected to the
binary input became
active (e.g. stuffing
box monitoring,
overpressure,
temperature switch).
4
yes
Limit
Stroke number
exceeded
L. STRK
¸
OFF
... the stroke counter
is reset or the
thresholds are
increased
The sum of the
distance covered by
the actuator exceeds
one of the set
thresholds.
5
yes
Direction change
limit exceeded
O. DCHG
¸
OFF
... the direction
change counter is
reset or the
thresholds are
increased
The number of
changes of direction
exceeds one of the
set thresholds.
6
yes
Lower limit stop
limit exceeded
F. ZERO
¸
OFF
39.YCLS = do or up
do
... the deviation of the
stop disappears or
the device was
re-initialized.
Wear of the valve
seat, deposit or
foreign matter in
the valve seat,
mechanical
misadjustment, friction
clutch misadjusted.
7
yes
Limit
of upper limit stop
exceeded
G. OPEN
¸
OFF
39.YCLS = up or up
do
... the deviation of the
stop disappears or
the device was
re-initialized.
Wear of the valve
seat, deposit or
foreign matter in
the valve seat,
mechanical
misadjustment, friction
clutch misadjusted.
8
no
Limit
Dead zone
adaptation
exceeded
E. DEBA
¸
OFF
34.DEBA = Auto
... the value has
fallen below the limit
again.
Increased stuffing box
friction, mechanical
batches of the
position feedback.
9
yes
Partial stroke test
exceeds reference
step time
A. PST
¸
OFF
... a partial stroke test
is performed
successfully within
the reference step
time or the function is
deactivated.
Valve jams or is
rusted in place,
increased friction
10
yes
General control
valve malfunction
b. DEVI
¸
OFF
... the position is back
within a narrow
corridor between
guide value and
model, or the function
is deactivated.
actuator fault, valve
fault, valve jams,
increased friction,
compressed air drop
11
yes
Pneumatic leakage C. LEAK
¸
OFF
... the leakage falls
below the set
thresholds, or the
function is
deactivated.
Pneumatic leakage
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...