Operation
117
SIPART PS2 Manual
A5E00074631--06
Monitoring of the lower temperature limit
The current temperature in the positioner housing is measured by a
sensor on the electronic circuit board. This parameter is for the
three-level monitoring of the lower temperature limit.
Temperature unit
The temperature unit can be switched over by pressing the Greater
Than or Smaller Than button between
°
C and
°
F. Another way of
switching over is the J1.TUNIT parameter for monitoring the upper
temperature limit. The selected unit applies to all temperature-related
parameters.
Threshold 1
First threshold for monitoring the lower temperature limit. The factory
setting is --25.0
°
C. If the temperature falls below the set value, the
threshold 1 error message is triggered.
Threshold 2
Second threshold for monitoring the lower temperature limit. The
factory setting is --30.0
°
C. If the temperature falls below the set value,
the threshold 2 error message is triggered.
Threshold 3
Third threshold for monitoring the lower temperature limit. The factory
setting is --40.0
°
C. If the temperature falls below the set value,
the threshold 3 error message is triggered.
H. TMIN
H1.TUNIT
H2.LEVL1
H3.LEVL2
H4.LEVL3
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...