Operation
104
SIPART PS2 Manual
A5E00074631--06
Example:
YNRM = FLOW with YA = 10 % and YE = 80 %
YNRM = MPOS or YNRM = FLOW
Presetting:
YA = 0% and YE = 100%
Input current
(setpoint)
X display
W display
X display
W display
X display
W display
Mechan. Stroke
(actual value)
Mechan. Stroke
(actual value)
Mechan. Stroke
(actual value)
0mm
0mm
0mm
80mm
80mm
80mm
16mm
16mm
16mm
32mm
32mm
32mm
48mm
48mm
48mm
64mm
64mm
64mm
0%
0%
0%
100%
100%
100%
20%
20%
20%
40%
40%
40%
50%
50%
50%
60%
60%
60%
80%
80%
80%
YE = 80%
YE = 80%
YE = 100%
YA = 10%
YA = 10%
YA = 0%
Example:
YNRM = MPOS with YA = 10 % and YE = 80 %
4mA
20mA
7.2mA
10.4mA
13.6mA
16.8mA
Input current
(setpoint)
Input current
(setpoint)
4mA
20mA
7.2mA
10.4mA
13.6mA
16.8mA
4mA
20mA
7.2mA
10.4mA
13.6mA
16.8mA
Figure 4-10
Dependence on the stroke of standardization and on YA and YE in the example of an 80 mm
linear actuator
Manipulated variable direction of action
The direction of action (rising or falling) of the display and the position
feedback (Iy) can be set with this.
Tight closing with manipulated variable (see figure 4-9, page 102)
With this function the valve can be driven to the seat with the maximum
actuating force of the actuator (continuous contact of the piezo-valves).
The tight closing function can be activated on one side or for both limit
positions. YCLS becomes active when the setpoint is below the value
set with parameter “YCDO” or above that set with parameter “YCUP”.
38.YDIR
39.YCLS
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...