Technical Data
151
SIPART PS2 Manual
A5E00074631--06
■
Technical specifications
Option modules
Without Ex protection
(EEx d also)
With Ex protection EEx ia/ib
With Ex protection EEx n
Ex protection to EN 50014, EN 50020 and
EN 50021
–
II 2G EEx ia/ib II C T4/T5/T6
II 3G EEx nA L [L] II C T6
Mounting location
–
Zone 1
Zone 2
Permissible ambient temperature for opera-
tion
(For devices with Ex protection: Only in con-
junction with the basic device 6DR5... -.E....
Only T4 is permissible when using I
y
module)
-30 ... +80 °C (-22 ... +176 °F)
T4: -30 ... +80 °C (-22 ... +176 °F)
1)
T5: -30 ... +65 °C (-22 ... +149 °F)
1)
T6: -30 ... +50 °C (-22 ... +122 °F)
1)
Alarm module
6DR4004-8A (without Ex protec-
tion)
6DR4004-6A (with Ex protection) 6DR4004-6A (with Ex protection)
Binary alarm outputs A1, A2 and alarm output
Signal status High (not responded)
Signal status Low* (responded)
(* Low is also the status when the basic
device is faulty or has not electric power sup-
ply)
Active, R = 1 k
Ω
, +3/-1%*
Disabled, I
R
< 60 µA
≥
2.1 mA
≤
1.2 mA
≥
2.1 mA
≤
1.2 mA
(* When used in the flameproof
casing the current consumption
is limited to 10 mA per output.)
(Switching threshold with sup-
ply to EN 60947-5-6: U
H
= 8.2 V,
R
i
= 1k
Ω
)
(Switching threshold with sup-
ply to EN 60947-5-6: U
H
= 8.2 V,
R
i
= 1k
Ω
)
Internal capacitance C
i
–
≤
5.2 nF
–
Internal inductance L
i
–
Negligible
–
Power supply U
H
≤
35 V
–
–
Connection to power circuits with
–
intrinsically safe switching
amplifier EN 60947-5-6
U
o
≤
15.5 V DC
I
k
≤
25 mA, P
≤
64 mW
U
i
≤
15.5 V DC
Binary input BE2
• Electrically connected to the basic device
- Signal status 0
Floating contact, open
Floating contact, open
Floating contact, open
- Signal status 1
Floating contact, closed
Floating contact, closed
Floating contact, closed
- Contact load
3 V, 5
µ
A
3 V, 5
µ
A
3 V, 5
µ
A
• Electrically isolated from the basic device
- Signal status 0
≤
4.5 V or open
≤
4.5 V or open
≤
4.5 V or open
- Signal status 1
≥
13 V
≥
13 V
≥
13 V
- Natural resistance
≥
25 k
Ω
≥
25 k
Ω
≥
25 k
Ω
Static destruction limit
±
35 V
–
–
Internal inductance and capacitance
–
Negligible
–
Connection to power circuits
–
Intrinsically safe U
i
≤
25.2 V
U
i
≤
25.2 V DC
Electrical isolation
The 3 outputs, the input BE2 and the basic device are electrically isolated from each other
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
SIA module (not for EEx d version)
6DR4004-8G (without Ex protec-
tion)
6DR4004-6G (with Ex protec-
tion)
6DR4004-6G (with Ex protec-
tion)
Limit transmitter with slot-type initiators and
alarm output
2-wire connection
Ex protection
Without
II 2 G EEx ia/ib IIC T6
II 3 G EEx nA L [L] IIC T6
Connection
2-wire system to EN 60947-5-6 (NAMUR), for switching amplifier to be connected on load side
2 slot-type initiators
Type SJ2-SN
Type SJ2-SN
Type SJ2-SN
Function
NC (normally closed)
NC (normally closed)
NC (normally closed)
Connection to power circuits with
nominal voltage 8 V
Current consumption:
≥
3 mA (limit value not
responded)
≤
1 mA (limit value
responded)
Intrinsically safe switching
amplifier EN 60947-5-6
U
i
≤
15.5 V DC
I
i
≤
25 mA, P
i
≤
64 mW
U
i
≤
15.5 V DC
P
i
≤
64 mW
Internal capacitance
–
≤
41 nF
–
Internal inductance
–
≤
100 mH
–
Electrical isolation
The 3 outputs are electrically isolated from the basic device
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
Alarm output
See Alarm module
See Alarm module
See Alarm module
1)
Only in conjunction with the basic device 6DR5...-E..... With Iy module only T4 permitted.
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...