Operation
138
SIPART PS2 Manual
A5E00074631--06
Fault indication
(symptoms)
possible cause(s)
Remedies
•
Actuator does not move
•
Compressed air < 1.4 bar
•
Set supply air pressure to
> 1.4 bar.
•
Piezo valve(s) do(es) not
switch (quiet “clicking” can
be heard however when
the + or – button is pressed
•
Reactor valve(s) closed
(screw(s) at the right-hand
stop)
•
Open reactor screw(s) (see
leaflet, figure “device view (6)”
by turning it/them
anti-clockwise.
the + or button is pressed
in manual mode).
•
Dirt in the pneumatic block
•
Repair (see chapter 5,
page 145) or new device;
integrated fine screen,
also replace and clean.
•
A piezo valve switches
continuously in stationary
automatic mode (constant
setpoint) and in manual
mode.
•
Pneumatic leakage in the
positioner – actuator system
Start leakage test in “RUN 3”
(initialization)!!!
•
Eliminate leakage in the
actuator and/or supply line
•
If the actuator is intact and the
supply line is leak-tight:
Repair (see chapter 5,
page 145) or new device
•
Dirt in the pneumatic block
(see above)
•
see above
Table 7
Fault indication
(symptoms)
possible cause(s)
Remedies
•
Both piezo valves switch
continuously and
alternately in stationary
automatic mode (constant
•
Too much slipstick of stuffing
box of control valve or actuator
•
Reduce slipstick or increase
dead zone of SIPART PS 2
(dEbA parameter) until
oscillation stops.
automatic mode (constant
setpoint) and in manual
mode, actuator oscillates
around a mean value.
•
Batches (play) in the positioner
-- actuator – control valve
system
•
Part--turn actuator:
Check if set screw of the
coupling wheel is inserted
firmly
•
Linear actuator:
Check if lever is connected
firmly to positioning shaft.
•
Eliminate any other play
between actuator and control
valve.
•
Actuator too fast
•
Increase actuating times via
reactor screws.
•
If fast actuating time is
required, increase dead zone
(dEBA parameter) until
oscillation stops.
•
SIPART PS 2 does not
“drive” control valve up to
the stop (at 20 mA).
•
Supply pressure too low.
•
Load of the feeding controller
or system output is too low.
•
Increase supply pressure
•
Interconnect load converter
•
Select 3/4 transmitter
operation
Table 8
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...