Preparing for Operation
80
SIPART PS2 Manual
A5E00074631--06
2. Set the parameter with the
-key to “turn”
Display:
3. Switch to the second parameter by pressing the operation mode
key
briefly. This has set automatically to 90
°
.
Display:
4. Switch on to the following display with the operation mode key
:
5. Start initialization by pressing the key
for longer than 5 s.
Display:
During the initialization phase “
RUN1
” to “
RUN5
” appear one after
another in the bottom display (see also structograms in figure 3-35,
page 83 to figure 3-38, page 86).
.
NOTE
The initialization process may last up to 15 minutes depending on the
actuator.
The initialization is complete when the following display
appears:
The top value indicates the total angle of rotation of the actuator
(example 93.5
°
).
The following display appears after pressing the operation mode key
briefly:
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...