Operation
122
SIPART PS2 Manual
A5E00074631--06
4.5 Diagnosis
4.5.1 Diagnostic display
To access the diagnostic display in automatic or manual mode,
press all three buttons for at least two seconds.
This following table gives an overview of the values that can be
displayed. The third column contains the term from which the
abbreviation is derived, unless it is self-explaining.
The structure of the diagnostic display is similar to that in “Configu-
ration” mode: the upper line shows the diagnosis value, the lower line
shows the number and abbreviation of the displayed value.
Use the operating mode button
to select the next diagnosis value.
By pressing and holding the operating mode button and simultaneously
pressing the decrement button
the diagnosis values can be
selected in reverse order.
Certain values can be set to zero by pressing the increment button
for at least 5 seconds. This is noted in the last table column.
Some diagnosis values can be greater than 99999. In this case, the
display switches to exponential indication. Example: the value for
1234567 is displayed as 1.23E6.
No. Abbre-
viation
Meaning
Values than
can be
indicated
Unit
Reset
possible
1
STRKS
Number of strokes (
Str
o
k
e
s
)
0 to 4.29E9
--
x
2
CHDIR
Changes of direction (
Ch
anges of
Dir
ection)
0 to 4.29E9
--
x
3
CNT
Number of fault messages (
C
ou
nt
er)
0 to 4.29E9
--
x
4
A1CNT
Number of alarms 1 (
A
larm
1 C
ou
nt
er)
0 to 4.29E9
--
x
5
A2CNT
Number of alarms 2 (
A
larm
2 C
ou
nt
er)
0 to 4.29E9
--
x
6
HOURS
Operating hours (
Hours
)
0 to 4.29E9
hours
7
WAY
Determined actuator travel (
Way
)
0 to 130
mm or
_
8
TUP
Actuating time up (Travel
T
ime
Up
)
0 to 1000
s
9
TDOWN
Actuating time down (Travel
T
ime
Down
)
0 to 1000
s
10
LEAK
Leakage (
Leak
age)
P 0.0 to 100.0
%
11
PST
Monitoring of the
P
artial
S
troke
T
est
OFF / ###.#,
fdini, notSt,
SdtSt, fdtSt,
notd, Strt
s for ###.#
12
PRPST
Time since the last
P
artial
S
troke
T
est
###, notSt,
Sdtst, fdtSt
days
13
NXPST
Time until the next
P
artial
S
troke
T
est
###, notSt,
SdtSt, fdtSt
days
14
DEVI
General control valve malfunction
Off, 0.0 to
100.0
%
15
ONLK
Pneumatic leakage
Off, 0.0 to
100.0
--
16
STIC
Slipstick effect
Off, --100.0 to
100.0
%
17
ZERO
Zero point offset
Off, --100.0 to
100.0
%
18
OPEN
Shifting the upper stop
Off, --100.0 to
100.0
%
19
PAVG
Average position value
0.0 to 100.0
%
20
P0
P
otentiometer value lower stop (
0
%)
0.0 to 100.0
%
Содержание SIPART PS2 6DR50 Series
Страница 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Страница 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Страница 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Страница 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Страница 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...