80
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
TECHNICAL DATA
9
9.1 General converter technical data
Technical features
Control mode
Closed-
loop vector
(VC)
Open-loop
vector
(SVC)
V/F
control
Control features
Startup torque
0.00Hz
180%
0.5Hz 150% 1.5Hz
150%
Speed adjust range
1:1000
1:100
1:50
Speed stabilizatio n
precision
± 0.02%
± 0.2%
±
0.5%
Torque control
Y
Y
N
Torque precision
± 5%
± 10%
—
Torque
response
time
<10ms
<20ms
—
Key
Function
Length control; Drooping control
S curve Acc./Dec; Autotuning; Torque
tracking
Switching Torque/ Speed control
mode; Multi-function I/O terminals
Undervoltage adjustment; Torque
limit; Multi-steps operation
Flying start, Slip compensation; Rich
PID; Simple PLC (On board)
Manual/auto torque boost; Current
limitation; AVR Function.
AC operation grounding switching
Freq. setting mode
Terminal pulse input (X4, X5)
Keypad,
terminal
up/down,
communication (host), analog input
AI1 AI2
Output Freq.
0.0~550.0Hz
Starting frequency
0.0~60.00Hz
Acc./Dec. time
0.1~3600s
Dynamic braking
400V Breaking unit action voltage
650~750V
200V Breaking unit action voltage
360~390V
DC braking
DC
braking
activation
frequency:0.00~550.0Hz;
Содержание SINAMICS V50