Parameter description
40
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.4 V/F Control Parameters
Code
Description
Setting range
Default Modify Modbus
Address
F4.00
V/F curve
setting
0: Constant torque
load V/F
1: 2.0 power
decreasing torque
2: 1.5 power
decreasing torque
3: 1.2 power
decreasing torque
4: Multiple dots V/F
0
X
0500H
F4.01
V/F freq. F1
0.0~F4.03
10.00Hz
X
0501H
F4.02
V/F voltage V1
0.0~100.0%
20.00%
X
0502H
F4.03
V/F freq. F2
F4.01~F4.05
25.00Hz
X
0503H
F4.04
V/F voltage V2
0.0~100.0%
50.00%
X
0504H
F4.05
V/F freq. F3
F4.03~F0.10
40.00Hz
X
0505H
F4.06
V/F voltage V3
0~100.0%
80.00%
X
0506H
F4.07
Torque boost
0.0%: Auto boost
0.1~30.0%: Manual
boost
0.00%
о
0507H
F4.08
Manual torque
boost cutoff
point
0.00~60.00Hz
50.00Hz
о
0508H
F4.09
Slip
compensation
coefficient
0.0~200.0%
0.00%
о
0509H
F4.10
Slip
compensation
filtering time
0.01~2.55s
0.20s
о
050AH
F4.11
V/F separation
control
voltage source
0: Disabled
1: Digital setting
(F4.12)
2: AI1
3: AI2
4: Pulse
5: Comm.
0
X
050BH
F4.12
V/F separation
voltage digital
setting
0V~max output voltage
380V
о
050CH
F4.13
V/F separation
voltage rising
time
0.0s~1000.0s
0.0s
о
050DH
Содержание SINAMICS V50