Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
PARAMETER DESCRIPTION
6
Note:
The value in the “[]” indicates the factory default value of the parameter.
6.0. Group 0 Basic Function
F0.00 Reserved
Range:
Drive type display
0-1 [0]
This parameter of SINAMICS V50 is reserved.
0:
Type G (Heavy duty)
1:
Type P (Normal duty)
F0.01 Control mode
Range: 0 - 2 [0]
0:
No vector Sensor vector control-1
This mode offers excellent vector control performance while insensitive to motor
parameters. It is applicable to most applications.
1:
No vector Sensor vector control-2
Precise speed sensor-less vector control technology realizes AC motor decoupling,
enabling the DC motorization of running control. It’s applicable to high performance
applications and features high precision of speed and torque and eliminates the need
for pulse encoder.
2:
Vector control with encoder
3:
V/F control
It is applicable to the common applications where load requirement is not high such
as fan and pump loads. It can be also used in applications where one drive drives
multiple motors.
F0.02 Run command control mode
Range: 0 - 2 [0]
0:
Operation keypad control (“LOCAL/REMOT” indicator OFF)
Running commands are controlled by RUN and STOP keys on operation keypad.
1:
Terminal control (“LOCAL/REMOT” indicator ON)
Running commands are controlled by the multifunctional input terminals such as
FWD, REV, JOGF, JOGR, etc.