Parameter description
32
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.2 Auxiliary running function group (F2)
Code Description
Setting range
Default
Modify
Modbus
Address
F2.00
Jog running
freq.
0.0 -50.00Hz
5.00Hz
о
0300H
F2.01
Jog Acc. time
0.0~3600.0s
20.0s
о
0301H
F2.02
Jog Dec. time
0.0~3600.0s
20.0s
о
0302H
F2.03
Acc. time2
0.0~3600.0s
20.0s
о
0303H
F2.04
Dec. time2
0.0~3600.0s
20.0s
о
0304H
F2.05
Acc. time3
0.0~3600.0s
20.0s
о
0305H
F2.06
Dec. time3
0.0~3600.0s
20.0s
о
0306H
F2.07
Acc. time4
0.0~3600.0s
20.0s
о
0307H
F2.08
Dec. time4
0.0~3600.0s
20.0s
о
0308H
F2.09
Skip freq. 1
0.00~320.0Hz
0.00Hz
х
0309H
F2.10
Skip freq. 2
0.00 320.0Hz
0.00Hz
х
030AH
F2.11
Skip freq.
amplitude
0.00 -15.00Hz
0.00Hz
х
030BH
F2.12
Anti-Reverse
control
0: Reverse
rotation allowed
1: Reverse
rotation not
allowed
0
о
030CH
F2.13
Fwd/ Rev switch
dead-zone time
0.0 3600s
0.0s
о
030DH
F2.14
Freq. lower-
limit treatment
0: Run with
frequency lower
limit
1: Zero
frequency
operation
0
х
030EH
F2.15
Reserved
Reserved
0
х
F2.16
Energy-saving
control select
0: Disable
1: Enable
1
о
0310H
F2.17
AVR Function
0: Disabled 1:
Enabled
2: Disabled only
at speed-down
2
X
0311H
F2.18
Over
modulation
0: Enabled
1: Disabled
1
X
0312H
F2.19
Droop control
0.00~10.00Hz
0.00Hz
о
0313H