Parameter description
36
SINAMICS V50 converter
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
6.3 Vector Control Parameters
Code
Description
Setting range
Default
Modify
Modbus
Address
F3.00
Speed loop
proportional
gain 1
1~3000
1000
О
0400H
F3.01
Speed loop
integral time 1
1~3000
300
о
0401H
F3.02
Switching
frequency 1
0.0~60.00Hz
5.00Hz
о
0402H
F3.03
Speed loop
proportional
gain 2
1~3000
800
о
0403H
F3.04
Speed loop
integral time 2
1~3000
200
о
0404H
F3.05
Switching
frequency 2
0.0~60.00Hz
10.00Hz
о
0405H
F3.06
Speed loop
filter time
constant
0~500ms
3ms
о
0406H
F3.07
Current loop
proportional
coefficient
0~6000
3000
о
0407H
F3.08
Current loop
integral
coefficient
0~6000
1500
о
0408H
F3.09
VC Slip
compensation
0.0~200.0%
100.00%
о
0409H
F3.10
Torque control
0: Torque
control Disabled
1: Torque
digital setting
(F3.11)
2: AI1
3: AI2
4: Pulse
5: Comm.
0
о
040AH
F3.11
Torque digital
setting
0.0~200.0%
50.00%
о
040BH
Содержание SINAMICS V50