Anti-condensation heating (option L55)
The anti-condensation heating is used at low ambient temperatures and high levels of humidity
to prevent condensation from forming. The heating is controlled via a thermostat.
The number of anti-condensation heaters is set in accordance with the number of cabinet
panels.
The converter monitors and signals if the external supply for the anti-condensation heating
fails.
See also
Safety instructions for maintenance (Page 193)
3.6.30
EMERGENCY STOP Category 1 (option L60)
Emergency Off, stop category1 (24 VDC) for controlled stop according to IEC60204.
In the standard version, Emergency Off stop category 0 is set for an uncontrolled stop. It also
has a function for disconnecting the drive from the power supply via the circuit-breaker. The
motor coasts down. The Emergency Off, stop category 1 function includes rapid stopping of
the drive using a deceleration ramp to be parameterized by the user. Voltage is then
disconnected from the drive as described for Emergency Off, stop category 0.
The EMERGENCY OFF button with protective collar is installed in the drive cabinet door.
WARNING
Danger from auxiliary voltages that are connected
When you press the EMERGENCY STOP button, the motor is stopped either uncontrolled
or controlled depending on the selected category 0 or 1, and the drive blocks the inverter, in
line with IEC60204-1 (VDE0113).
Auxiliary voltages such as those for separately-driven fans or anti-condensation heating are
still present. Certain areas within the drive also remain under voltage, e.g. the control function
or auxiliaries. When touching these auxiliary voltages, this can result in death or serious
physical injury.
Ensure that the EMERGENCY OFF button is integrated in the safety system for the whole
machine so that all the voltages are completely disconnected. For this purpose, an NC contact
is installed at terminals =.LA–X51:1A or 1C and =.LA–X51:2A or 2C.
Description
3.6 Description of options
SINAMICS GM150 6SL3815-2LN41-4AA2
66
Operating Instructions 04/2017
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......