![Siemens SINAMICS GM150 Скачать руководство пользователя страница 178](http://html.mh-extra.com/html/siemens/sinamics-gm150/sinamics-gm150_operating-and-installation-instructions_378206178.webp)
S>@
Set TM31.AO_char. x2 to 100.00 %.
S>@
Set TM31.AO_char. y2 to 10.000 V.
8.4.2.5
Scaling the input signal of the analog inputs
In addition to the expanded setting options of the analog inputs, a function for scaling the input
signal is available.
Adjustable parameters of the scaling
Parameter
Value
Adjustment range
p4057[0]
Analog inputs, characteristic value x1
-20,000 to 20,000 V or mA
Default settings: 0,000 mA
Setting for the x coordinate in V or mA of the first point on the scaling characteristic.
When analog input 0 is set as a voltage input (p4056 = 0 / 4) and switch S5.0 is set to "V", the unit is
V.
When analog input 0 is set as a current input (p4056 = 2 / 3 / 5) and switch S5.0 is set to "I", the unit
is mA.
Parameter
Value
Adjustment range
p4058[0]
Analog inputs, characteristic value y1
-1000.00 to 1000.00%
Default settings: 0,0 %
Setting for the y coordinate in % of the first point on the scaling characteristic.
Parameter
Value
Adjustment range
p4059[0]
Analog inputs, characteristic value x2
-20,000 to 20,000 V or mA
Default settings: 0.000 mA
Setting for the x coordinate in V or mA of the first point on the scaling characteristic.
When analog input 0 is set as a voltage input (p4056 = 0 / 4) and switch S5.0 is set to "V", the unit is
V.
When analog input 0 is set as a current input (p4056 = 2 / 3 / 5) and switch S5.0 is set to "I", the unit
is mA.
Operation
8.4 Functions
SINAMICS GM150 6SL3815-2LN41-4AA2
178
Operating Instructions 04/2017
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......