![Siemens SINAMICS GM150 Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/siemens/sinamics-gm150/sinamics-gm150_operating-and-installation-instructions_378206037.webp)
3.5.3
Precharging
To prevent overcurrents and temporary overvoltages in the DC link when the line voltage is
connected, the DC-link capacitors must be precharged. The DC link is precharged via the
auxiliary supply.
The precharging circuit comprises the following components:
● Precharging transformer
● Diode bridge
● Precharging resistors
● Contactor for switching on and off
● Circuit-breaker
Detailed information about interconnecting the precharging components is provided in the
circuit manual. The component mounting locations are provided in the layout diagram.
Designation
Value
Precharging time
1)
25 s
Precharging current in three-phase 400 V supply
with 4.16 kV parallel connection and 6 kV
with 2.3 kV; 3.3 kV; and 4.16 kV single connection
30 A
20 A
Discharging time of the DC link T
DISCH
1)
≈ 300 s
1)
The precharging time can vary depending on the system
3.5.4
Electromechanical door interlock system
The electromechanical door interlock system is designed to protect personnel, and is an
integral part of the safety concept. During operation and when the make-proof grounding switch
is open, all the doors are interlocked (with the exception of the door for the control section).
The electromechanical door interlock system ensures that the doors for the power unit cannot
be opened when the DC link voltage is above a defined threshold value. The control only
releases the door interlocking once the circuit breaker is safely open and the grounding switch
is closed. You can open the doors once released by the control.
The device cannot be switched on again until all the doors are closed. The doors remain
interlocked if the auxiliary voltage fails. For more information, refer to the Chapter
"Maintenance"
See also
Description
3.5 Description of the components
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
37
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......