Device commissioning menu
This expert menu supports the device commissioning controlled via p0009.
1. Select a commissioning level.
– The parameters that can be written in the enabled commissioning level are displayed.
This makes it easier for you to make changes, such as switching over units or activating
function modules.
2. Set the p0009 parameter to 0: Ready to finish commissioning.
Ⴍ
+HOS
%DFN
2.
'HYLFHFRPPLVVLRQLQJS
'DWDVHWEDVHFRQILJXUDWL
5HDG\
'HYLFHFRQILJXUDWLRQ
'HILQLWLRQRIGULYHW\SH
'ULYHEDVHFRQILJXUDWLRQ
3. Press the <▲> or <▼> function key to select the desired parameter. Confirm the selection
with <OK>.
● 0: Ready = The device commissioning is closed.
● 1: Device configuration = At the first commissioning of the device, after start-up, the device
is in the "device configuration" status. Transfer the identification for the actual topology
(r0098) to the identification for the setpoint topology (p0099). To do this, it is sufficient to
set a single index value of p0099[x] the same as r0098[x]. No other parameter may be
changed prior to the commissioning. To start the internal automatic first device
commissioning, set p0009 = 0 (ready). After the first commissioning has been carried out,
in this status, other basic device configuration parameters can be adjusted (e.g. the basic
sampling time in p0110) if required.
● 2: Specification of the drive type = You can change or select the drive object types and/or
the function modules for individual drive objects. To do this, set the drive object type with
p0107[0...15] and the function module with p0108[0...15]. Further details can be found in
the parameter p0101[0...15].
● 3: Drive basic configuration = After the device has been commissioned for the first time,
basic changes can be made for the individual drive objects (e.g. sampling times in p0111,
p0112, p0115 and the number of data sets in p0120, p0130, p0140, p0170, p0180).
● 4: Data basis configuration = After the first commissioning of the device, you can change
the individual drive objects:
– Assignment of the components (p0121, p0131, p0141, p0151, p0161) to the individual
data sets.
– Assignment of the power unit, motor and encoder to the drive data sets (p0185, ...).
● 30: parameter reset = In order to bring the complete unit into the "first commissioning" status
or to load the parameters saved with p0977, p0009 must first be set to this value. p0976
can then be changed to the required value.
You will find a list of the settable parameters below.
Operation
8.2 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
149
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......