6.5.5
Connecting ground
DANGER
Insufficient grounding
The drive must be grounded to ensure that it operates safely and reliably. If the drive is
operated with insufficient grounding, then the protection and monitoring functions can fail.
Death, serious injury, or material damage will result.
To ensure the correct functioning of the protection and monitoring equipment, ground the
device.
Each cabinet has a grounding lug for grounding the components installed in the cabinet. It is
located at the bottom of the cabinet. Connect the cabinets securely to the plant grounding
system via these grounding lugs.
Figure 6-6
Grounding lug
6.5.6
Connect the auxiliary voltage
Connect the auxiliary voltage 1-phase 230 VAC / 50 Hz
Connect the auxiliary voltage for, e.g. SITOP, GSV, closed-loop control, open-loop control, to
the terminal strip
①
. The maximum permissible conductor cross-section is 4 mm
2
.
With options C30 - C49, the auxiliary voltage can be drawn from the matching transformer.
You will find notes in the circuit manual of the drive.
Electrical connection
6.5 Connection
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
111
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......