You use p1242 to define the starting point of the vdc-max controller. The starting point is the
maximum value of the DC link voltage that cannot be exceeded. If the DC link voltage is below
the starting point, the controller remains inactive. The controller gain can be changed by means
of p1250. The set ramp-down remains inactive while the vdc_max controller is active. The
ramp-down time increases the more excess kinetic energy is stored in the drive train.
8.4.3.5
Fan monitoring
Monitoring the fan ensures that the device functions safely. If the cooling is insufficient, an
alarm is output.
8.4.3.6
Speed monitoring with incremental encoder
Permanent speed monitoring enables motor control without an encoder. You can upgrade with
additional incremental encoders under the following conditions:
● When high-performance applications, such as bearing control, require a permanent speed
control.
● For long-continuing applications with low speeds.
8.4.3.7
Controlled stop, EMERGENCY STOP category 1
The EMERGENCY OFF function for controlled shutdown stops the drive by means of a quick
stop process along a deceleration ramp that must be parameterized.
Note
The drive is stopped during controlled deceleration without braking modules with only a very
low % braking torque. Depending on the load machine, the ramp-down procedure may take a
long time.
Connections of the EMERGENCY STOP button
Most of the contacts of the EMERGENCY STOP button are integrated in the control circuit of
the circuit-breaker. The two remaining normally-closed contacts of the EMERGENCY STOP
button are situated on the terminal block.
EMERGENCY
STOP button
Where connected
=.LA-S31:11-12
=.LA-S31:21-22
=.LA-S31:31-32
Circuit breaker con‐
trol circuit
=.LA-X11:9-10
=.LA-X11:5-6
=.LA-X11:7-8
If jumpered STOP; if not jumpered
EMERGENCY OFF (produces an
instantaneous stop command on
the circuit-breaker)
=.LA-S31:51-52
EMERGENCY STOP
customer
=.LA-X51:1, 2
=.LA-S31:61-62
Excitation equipment =.LA-X51:3, 4
Max. connectable cross-section: 4 mm² (AWG 10)
You will find further information in the section "Circuit book" in your operating instructions.
Operation
8.4 Functions
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
183
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......