Technical data
6.4 400 V converters
Power Module PM240P-2
62
Hardware Installation Manual, 06/2020, A5E37800827C AD
6.4.3
Current derating depending on the pulse frequency, 400 V converters
Article number
LO
power
[kW]
LO base load output current [A]
Pulse frequency [kHz]
2
4
*)
6
8
10
12
14
16
6SL3210-1RE24-5 . L0
22
45
45
38.3
31.5
27
22.5
20.3
18
6SL3210-1RE26-0 . L0
30
60
60
51
42
36
30
27
24
6SL3210-1RE27-5 . L0
37
75
75
63.8
52.5
45
37.5
33.8
30
6SL3210-1RE28-8 . L0
45
90
90
76.5
63
54
45
40.5
36
6SL3210-1RE31-1 . L0
55
110
110
93.5
77
---
---
---
---
Pulse frequency [kHz]
2
*)
4
6
8
10
12
14
16
6SL3210-1RE31-5 . L0
75
145
145 123.3 101.5
---
---
---
---
6SL3210-1RE31-8 . L0
90
178
178 151.3 124.6
---
---
---
---
6SL3210-1RE32-1 . L0
110 205 143.5
---
---
---
---
---
---
6SL3210-1RE32-5 . L0
132 250
175
---
---
---
---
---
---
*) Factory setting
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected