Technical data
6.5 690 V converters
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
67
6.5.3
Current derating depending on the pulse frequency, 690 V converters
Article number
LO
power
[kW]
LO base load output current [A]
Pulse frequency [kHz]
2
4
6SL3210-1RH21-4 . L0
14
8.4
6SL3210-1RH22-0 . L0
19
11.4
6SL3210-1RH22-3 . L0
23
13.8
6SL3210-1RH22-7 . L0
27
16.2
6SL3210-1RH23-5 . L0
35
21
6SL3210-1RH24-2 . L0
42
25.2
6SL3210-1RH25-2 . L0
52
31.2
6SL3210-1RH26-2 . L0
62
37.2
6SL3210-1RH28-0 . L0
80
48
6SL3210-1RH31-0 . L0
100
60
6SL3210-1RH31-2 . L0
115
69
6SL3210-1RH31-4 . L0
142
85.2
The permissible motor cable length depends on the cable type and the selected pulse frequency.