Technical data
6.7 Restrictions for special ambient conditions
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
71
Permissible line supplies dependent on the installation altitude
●
For installation altitudes ≤
2000 m above sea level, it is permissible to connect the
converter to any of the line supplies that are specified for it.
●
For installation altitudes 2000 m ... 4000 m above sea level, the following applies:
–
Connection to a TN line system with grounded neutral point is permissible.
–
TN systems with grounded line conductor are not permitted.
–
The TN line system with grounded neutral point can also be supplied using an
isolation transformer.
–
The phase-to-phase voltage does not have to be reduced.
Note
Using Power Modules connected to TN line supplies with voltages ≥
600 V for installation
altitudes 2000 m … 4000 m
For voltages ≥ 600 V, the TN line supply must have a grounded neutral point established
using an isolating transformer.