Technical data
6.5 690 V converters
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
63
6.5
690 V converters
6.5.1
General data, 690 V converters
Property
Version
Line voltage
3 AC 500 V … 690 V ± 10% (in operation -20% < 1 min)
with Class J fuses, maximum 600 V
Line system configurations Grounded TN/TT line systems or non-grounded IT line systems
Line impedance
Uk < 4%, line reactor is not required
Power factor λ
> 0.9
Output voltage
3 AC 0 V … 0.95 × input voltage (max.)
Input frequency
50 Hz … 60 Hz, ± 3 Hz
Output frequency
0 … 550 Hz, depending on the control mode
Inrush current
< LO base load input current
Overvoltage category ac-
cording to EN 61800-5-1
III for line supplies
Pulse frequency
2 kHz (factory setting), can be adjusted to 4 kHz
If you increase the pulse frequency, the converter reduces the maximum output current.
Short-circuit current rating
(SCCR) and branch protec-
tion
≤ 100
kA rms
Branch protection and short-circuit strength according to UL and IEC
https://support.industry.siemens.com/cs/ww/en/view/109479152
Braking methods
DC braking, compound braking
Degree of protection ac-
cording to EN 60529
IP20; must be installed in a control cabinet
Protection class according
to EN 61800-5-1
The converters are devices with protection class I
Touch protection according
to EN 50274
DGUV regulation 3 when used for the intended purpose
Cooling in compliance with
EN 60146
Forced air cooling AF