Transport, Unpacking, Installation
12.96
2-2
Siemens AG 6SE7087-6BM70
SIMOVERT MASTER DRIVES Operating Instructions
2.3 Mounting
The following are required for mounting:
♦
M8 bolt(s)
♦
Dimension drawings:
Fig. 2.1 for type of construction J, Fig. 2.2 for type of construction K and
Fig. 2.5 for type of construction M.
♦
Only type of construction M: Engineering support
WARNING
Safe converter operation requires that the equipment is mounted and commissioned by
qualified personnel taking into account the warning information provided in this Instruction
Manual.
The general and domestic installation and safety regulations for work on electrical power
equipment (e.g. VDE) must be observed as well as the professional handling of tools and
the use of personnal protective equipment.
Death, severe bodily injury or significant material damage could result if these instructions
are not followed.
Chassis units do not provide any protection against direct contact. It is the users
responsibility to ensure and provide the correct protection against contact according to the
relevant accident prevention regulations VBG4, by appropriately designing the enclosure or
enclosures around the chassis unit.
Remove shipping brace (marked).
The three units, type of construction M with degree of protection IP00, must be assembled according to the
instructions specified in the engineering support documentation.
The control connections between the master and slave must then be established.
♦
Procedure: The control cables must be carefully routed through the cable duct in the reactor chassis in the
master cabinet.
•
Insert connectors -X238 / -X234 / -X32 / -X42.
•
Insert the fiber-optic cables U41 / U51 / U61 / U42 / U43 / U52 / U53 / U62 / U63 in the
master, at the IPI.
NOTE
Inserting the fiber-optic cables:
Insert the fiber-optic cable up to its end stop (approx. 16 mm), tighten up
the union nut by hand.
CAUTION
Fiber-optic cables may not be bent through a sharp angle.
Bending radius for fiber-optic cables
≥
30 mm.
The unit is mounted corresponding to the dimension drawings in Section 2.4.