Technical Data
12.96
9-2
Siemens AG 6SE7087-6BM70
SIMOVERT MASTER DRIVES Operating Instructions
Inverter types
6SE70... 35-1TJ20 36-0TK20 37-0TK20 38-6TK20 41-1TK20 41-1TM20 41-3TM20
Rated voltage, rated frequency, rated current
Rated voltage in V
n
Input
Output
V
DC 510 ... 620 ±15 %
3 AC 0 ... Rated voltage / 1.35
Rated frequency f
n
Input
Output:
U/f = konst
U = konst
Hz
0 ... 600
8 ... 300
Rated current I
n
Input
Output
A
607
510
702
590
821
690
1023
860
1309
1100
1309
1100
1547
1300
DC link voltage V
dn
V
= Rated voltage
Rated output
kVA
336...406 388...470 454...550 566...685 724...876 724...876 856...1036
Auxiliary power supply
DC 24 V (20 V - 30 V)
A
5 without Options;
with Options refer to
Section 6.1
5 + 3 without Options;
with Options refer to
Section 6.1
Auxiliary power supply
V
AC 230
±
15%
Loading Class II acc. to EN 60146-1-1
Rated current
A
464
538
628
783
1001
1001
1183
Base load time
s
240
Overcurrent
A
694
802
938
1169
1496
1496
1768
Overcurrent time
s
60
Losses, cooling, power factor
Power factor
Converter cos
ϕ
U
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
<
0.92 ind.
Efficiency
η
−
Pulse frequency 2.5 kHz
0.98
0.98
0.98
0.98
0.98
0.98
0.98
Power loss
−
Pulse frequency 2.5 kHz
kW
6
8
9
10
16
15
17
Required cooling air flow
m
3
/s
0.6
0.75
0.75
0.75
0.92
1.5
1.5
Pressure drop
∆
p
Pa
350
640
640
640
950
640
640
Sound pressure level, dimensions, weights
Sound pressure level
dB(A)
80
83
83
83
85
85
85
Type
J
K
K
K
K
M
M
Width
for IP00
Height
Depth
mm
800
1400
550
800
1750
550
800
1750
550
800
1790
550
800
1790
550
2300
1910
580
2300
1910
580
Ground
−
IP00
kg
350
520
520
520
535
ca. 1500
ca. 1500
Required current for fan (typical)
230 V / 50 Hz
A
2.6
5.2
5.2
5.2
13.4
10.4
10.4
230 V / 60 Hz
A
3.4
6.7
6.7
6.7
20.0
13.4
13.4