Installation
64
REVISION 02 * INSTALLATION SIMOSEC * 832-6063.0
14
Installing and connecting low voltage equipment
14.1
Installing secondary cables
The secondary cables are routed above the control compartment behind the screwed-on
cover.
The secondary cables can be installed directly into the terminal connection compartment
either from above through an entrance bushing or conduit fitting or from below through a
flexible metal conduit (not furnished) arranged along the switchgear frame.
Please observe the correct polarity of the secondary leads of the window-type current
transformers to be connected.
14.2
Connecting low voltage wiring
Connect all customer low voltage wiring according to the terminal plug and cable
designations of the circuit diagrams of the switchgear.
14.3
Connecting the space heater
The individual panels of SIMOSEC switchgear are equipped with a space heater to
prevent condensation.
Ö
Connect the space heater terminal according to the circuit diagrams for the
switchgear.
Fig. 52:
Cable routing for customer low voltage wiring
a
Panel
s
Cover, screwed on
d
Entry area for secondary cables
f
Metal duct for secondary cables (option)
g
Terminal connection compartment for customer
low voltage wiring
h
Low voltage compartment
j
Control compartment
Rating
100 W