Installation
12.2
Aligning the panel and fastening to the foundation
Aligning the panel
Observe the minimum distances to the side and rear wall of the switchgear room in
accordance with the switchgear arrangement drawing. For the dimensions and
minimum distances of the panels, please refer to the dimension drawing and
arrangement diagram for the switchgear.
The switchgear may have a level difference of 0.04 in/yd (1 mm/m) as a maximum.
Ö
Align the panel in horizontal position.
Ö
Align the panel in vertical position.
Check to assure that the panel is aligned (levelled to a maximum level difference of
0.04 in/yd (1 mm/m).
Fastening the panel to the
foundation
Fasten the panel to the foundation at 4 points at least.
There are two possibilities for fastening the panel to the foundation :
• bolting to sill channels (not furnished)
• bolting to foundation inserts (not furnished)
Fig. 34:
Bolting to sill channel
a
Base frame of the panel
s
Sill channel
d
Insert
f
Foundation
g
Washer (inner diameter 10.5 mm,
outer diameter
W
31.5 mm)
h
Screw with contact washer
Fig. 35:
Bolting to foundation inserts