Description
24
REVISION 02 * DESCRIPTION SIMOSEC * 832-6063.0
For the ready-for-service indicator, a gas-tight measurement box is installed on the inside
of the switchgear vessel.
A coupling magnet, which is fitted to the bottom end of the measurement box, transmits
its position to an outside armature through the non-magnetic switchgear vessel. This
armature moves the ready-for-service indicator of the switchgear.
While changes in the gas density during the loss of gas, which determines the dielectric
capability, are displayed, changes in the gas pressure due to temperature and external
pressure variations are not. The gas in the measurement box has the same temperature
as that in the switchgear.
The temperature effect is compensated via the same pressure change in both gas
volumes.
8.11
Voltage detection systems
Voltage detection systems are provided for verification of safe isolation from supply.
Regular tests of the voltage detection systems must be performed by the user and
documented.
Voltage detection systems according to IEC 61243-5 and EN 61243-5 (VDE 0682-415)
with:
• HR system (standard)
• LRM system (option)
• Integrated voltage detection system CAPDIS-S1/-S2 (option)
• -C1: capacitance integrated into bushing or post insulator
• -C2: capacitance of the connection leads and of the voltage indicator to ground
Fig. 21:
Voltage detection system via capacitive voltage divider (phase L3 shown)
a
HR indicator, plug-in type