Installation
58
REVISION 02 * INSTALLATION SIMOSEC * 832-6063.0
Mounting of the cold shrink
Ö
Pull the cold shrink insulation over the cable termination. The loose pull tab of the
cold shrink insulation must point away from the switchgear cable connection
terminal.
Ö
Bolt the the high voltage cable together with the cable connection terminal
(tightening torque 37 lbf·ft or 50 Nm).