Fail-Safe Blocks
Fail-Safe Systems
8-92
A5E00085588-03
8.8
Comparison Blocks for Two Input Values of the Same
Type
Block
Description
F_LIM_HL
Monitoring for upper limit violation of a REAL value
F_LIM_LL
Monitoring for lower limit violation of a REAL value
F_2oo3_R
Selects median of 3 REAL values
F_1oo2_R
Selects between 2 REAL values based on diagnostics
8.8.1 F_LIM_HL
Function
This block monitors the input variable U for limit violation (U_HL). A hysteresis can
also be specified to avoid fluttering of the output QH in the event of fluctuations of
the input value.
•
U
≥
U_HL: In the event of violation of the upper limit, the output QH = 1.
•
(U_HL – HYS)
≤
U < U_HL: QH remains unchanged in this range.
•
U < (U_HL – HYS): In the event of violation of the lower limit (hysteresis), the
output QH = 0.
The limit and hysteresis are also available as non-fail-safe data at the outputs
U_HL_O and HYS_O for further processing in the standard program. The
hysteresis can be used to avoid fluttering of QH if the input value U fluctuates by
the limit value U_HL.
If either input variable U, U-HL or HYS contains an invalid REAL number, the
Substitute Input (SUBS_IN) will be passed directly to the output (QH).
If an invalid REAL number is generated during the calculations involving U, U-HL
and HYS, the output QH=1.
The output QHN corresponds to the negating output QH.
Note
The non-fail-safe outputs can be made available to the standard program without a
conversion block.
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...