Programming
Fail-Safe Systems
5-48
A5E00085588-03
5.4.7
Downloading the Entire Safety Program
Procedure
To download the Safety Program to the PLC, proceed as follows:
1.
Switch the CPU to STOP mode.
2.
Choose the PLC > Download > Entire Program menu command in CFC.
Note
Before the Safety Program is downloaded, the CPU password is requested if
changes are detected in the fail-safe program section.
Result: If you enter the correct password, the Safety Program is downloaded to the
CPU to which the program container is assigned. If the password is entered
incorrectly, the download operation is not executed.
After the program has been downloaded to the CPU, you have to compare the
overall signature of the program in the CPU with the overall signature in the
accepted printout (see "Checking the Overall Signatures" in the section entitled
"Initial Acceptance of a Safety Program"). In the case of S7 FH systems, you have
to make this comparison for both CPUs.
Working With Programs on a Memory Card
If you use the Safety Program on a memory card, remember the following:
!
Safety Note – Safety Program on Memory Card
•
Before you switch the S7 F System to RUN mode, compare the
overall signature of the program on the flash EPROM memory
card with the overall signature of the reference data. If necessary,
identify the memory card with the overall signature.
•
In the case of a fault-tolerant S7 FH System, make sure that the
memory cards of the redundant CPUs are of the same type - RAM
or flash EPROM – and that the same Safety Program is on the
redundant flash EPROM memory cards.
•
Ensure there is access protection regulating the removal and
insertion of memory cards.
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...