Programming
Fail-Safe Systems
A5E00085588-03
5-19
6.
Optional: Interconnect the QBAD output to find out if a substitute value or valid
process value is output. Value status (quality code) of the process value
7.
Optional: Evaluate the QUALITY output in the standard program or on the OS
to obtain or find out the quality code of the process value.
8.
Interconnect the relevant ACK_REI input with the signal for the
acknowledgment of reintegration (see "Passivation and Reintegration").
9.
Interconnect the simulation I/Os (optional, see "Simulation Mode").
10. Interconnect the diagnostic outputs DIAG_1/DIAG_2 of the F module drivers
F_M_DI8 or F_M_DI24 if you want to evaluate in the standard program
whether discrepancy errors have occurred (optional, see Descriptions of the F
Driver Blocks). You can use this information to program messages about
discrepancy errors to the OS.
11. Place and interconnect the F module drivers manually or automatically.
Note
You can read out byte 0 of DIAG_1/DIAG_2 for service purposes in the event of an
error in CFC test mode.
Placing and Interconnecting the F Module Drivers Automatically
You have two options:
•
At any time before you compile the Safety Program :
In Simatic Manager, choose the Options > Charts > Generate Module
Drivers menu command. Open the Properties dialog box and make sure that
the PCS 7 Drivers\PCS 7 Drivers\Blocks library is set. Confirm by clicking OK
twice.
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...