Safety
Fail-Safe Systems
A5E00085588-03
7-13
Time
Description
Where to Find it?
TCiR,F_SEND
CiR Synchronization Time of the CPU with the call of
F_SENDBO or F_SENDR:
- From the CiR-Object parameters in STEP7
- Summarize all CiR-Object synchronization times of
the simultaneously changing DP buses and place total
here. If CiR is not used, enter 0.
Properties of the CiR_Object
in HWCONFIG.
For additional information,
refer to section 4.8.4
"Configuration in Run (CiR)".
TCiR,F_RCV
CiR Synchronization Time of the CPU with the call of
F_RCVBO or F_RCVR:
-From the CiR-Object parameters in STEP7
-Summarize all CiR-Object synchronization times of the
simultaneously changing DP buses and place total
here. If CiR is not used, enter 0.
Properties of the CiR_Object
in HWCONFIG.
For additional information,
refer to section 4.8.4
"Configuration in Run (CiR)".
Finding TUSEND
You can download a tool for calculating the TUSEND value from the Internet at:
http://www4.ad.siemens.de/view/cs/de/1651770
Contribution ID 1651770
Note
To activate the monitoring of the maximum communication delay
when the standby in the FH system is updated, you must assign this
parameter a value in HWCONFIG (CPU properties, "H Parameters"
tab).
Simultaneous updating in both CPUs is not assumed.
7.4.2.4 Monitoring of Safety-Related Communication Between F-run-time
Groups
Time monitoring takes place in the FBs F_R_BO and F_R_R and is assigned there
at the TIMEOUT input parameter.
To ensure that time monitoring is not triggered when there are no faults, the
TIMEOUT monitoring time must be at least as large as the larger of the two
maximum cyclic interrupt cycle times of F_S_R and F_S_BO or F_R_R and
F_R_BO:
TIMEOUT > MAX(TCimax, F_S; TCImax, F_R)
Note the following:
Time
Description
Where to Find it?
TCImax, F_S
Maximum cycle time of the cyclic interrupt OB with the
call of F_R_BO or F_R_R
Monitoring the F Cycle Time
section
TCImax, F_R
Maximum cycle time of the cyclic interrupt OB with the
call of F_S_BO or F_S_R
Monitoring the F Cycle Time
section
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...