Fail-Safe Blocks
Fail-Safe Systems
8-44
A5E00085588-03
8.4.9 F_FTI_TI
Function
This block converts the F-data type F_TIME into the standard data type TIME,
since individual structure elements of the F-data type cannot be accessed
separately in the CFC chart. This enables signals formed in the Safety Program
section to be further processed in the standard program section.
This block must be placed in the standard program section.
I/Os
Name
Data Type
Explanation
Default
Input:
IN
F_TIME
Input variable
T#0 ms
Output:
OUT
TIME
Output variable
T#0 ms
Error Handling
None