Programming
Fail-Safe Systems
5-56
A5E00085588-03
5.4.10
Testing the Safety Program
After compilation and downloading, you can test the program. You can test Safety
Programs by switching to test mode in CFC using the Test > Test Mode menu
command. In test mode you are connected to the automation system (CPU) online.
Rules for Testing
!
Safety Note – Safety Program disable if change to failsafe outputs
You can observe the Safety Programs in CFC test mode and change non-
interconnected inputs of fail-safe blocks. Online changes to fail-safe outputs and
automatically assigned I/Os are not permitted and result in a Safety Program
disable.
!
Safety Note – ES changes can change signature
When you use the ES, changes to non-safety-related parameters can result in a
change to the overall signature of the offline Safety Program. This means that the
Safety Program might have to be accepted again after the test. To ensure that the
overall signature of the Safety Program remains unchanged, you must undo any
parameter changes by reassigning the original values to the parameters.
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...