Technical specifications
A.3 Digital inputs and outputs expansion modules (EMs)
S7-200 SMART
734
System Manual, V2.3, 07/2017, A5E03822230-AF
Table A- 84 Digital outputs
Model
EM Digital
8 x Inputs/
Digital 8 x Outputs
(EM DT16)
EM Digital
8 x Inputs/
8 x Relay Outputs
(EM DR16)
EM Digital
16 x Inputs/ Digital
16 x Outputs
(EM DT32)
EM Digital
16 x Inputs/
16 x Relay Outputs
(EM DR32)
Number of outputs
8
8
16
16
Type
Solid state-
MOSFET (sourcing)
Relay, dry contact
Solid state-
MOSFET (sourcing)
Relay, dry contact
Voltage range
20.4 to 28.8 V DC
5 to 30 V DC or
5 to 250 V AC
20.4 to 28.8 V DC
5 to 30 V DC or
5 to 250 V AC
Logic 1 signal at max. current
20 V DC, min.
--
20 V DC, min.
--
Logic 0 signal with 10 KΩ load
0.1 V DC, max.
--
0.1 V DC, max.
--
Rated current per point (max.)
0.75 A
2 A
0.75 A
2 A
Rated current per common
(max.)
3 A
8 A
6 A
8 A
Lamp load
5 W
30 W DC/200 W AC 5 W
30 W DC/200 W AC
ON state contact resistance
0.6 Ω max.
0.2 Ω max. when
new
0.6 Ω max.
0.2 Ω max. when
new
Leakage current per point
10 μA max.
--
10 μA
max.
--
Surge current
8 A for 100 ms max. 7 A with contacts
closed
8 A for 100 ms max. 7 A with contacts
closed
Overload protection
No
No
No
No
Isolation (field side to logic)
500 V AC for 1
minute
1500 V AC for 1
minute (coil to con-
tact)
None (coil to logic)
500 V AC for 1
minute
1500 V AC for 1
minute (coil to con-
tact)
None (coil to logic)
Isolation resistance
--
100 M
Ω min. when
new
--
100 M Ω min. when
new
Isolation between open contacts --
750 V AC for 1
minute
--
750 V AC for 1 mi-
nute
Isolation groups
2
2
3
4
Inductive clamp voltage
Minus 48 V
--
Minus 48 V
--
Switching delay
50 μs max., off to
on
200 μs max., o
n to
off
10 ms max.
50 μs max., off to
on
200 μs max., on to
off
10 ms max.
Lifetime mechanical (no load)
--
10,000,000
open/close cycles
--
10,000,000
open/close cycles
Lifetime contacts at rated load
--
100,000 open/close
cycles
--
100,000 open/close
cycles
Output behavior in STOP
Last value or substi-
tute value (default
value 0)
Last value or substi-
tute value (default
value 0)
Last value or substi-
tute value (default
value 0)
Last value or substi-
tute value (default
value 0)
Number of outputs on simulta-
neously
8
8
16
16
Cable length (max.), in meters
Shielded: 500 m
Unshielded: 150 m
Shielded: 500 m
Unshielded: 150 m
Shielded: 500 m
Unshielded: 150 m
Shielded: 500 m
Unshielded: 150 m
Содержание SIMATIC S7-200
Страница 30: ...Product overview 1 7 Programming software S7 200 SMART 30 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 267: ...Program instructions 7 6 Counters S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 267 HSC modes 3 and 4 ...
Страница 394: ...Program instructions 7 18 Subroutine S7 200 SMART 394 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 425: ...Communication 8 5 PROFIBUS S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 425 ...
Страница 786: ...Technical specifications A 11 S7 200 SMART cables S7 200 SMART 786 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 798: ...Error codes C 4 PLC fatal error codes S7 200 SMART 798 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 848: ...Ordering information F 6 Human Machine Interface devices S7 200 SMART 848 System Manual V2 3 07 2017 A5E03822230 AF ...