Program instructions
7.9 PID
S7-200 SMART
310
System Manual, V2.3, 07/2017, A5E03822230-AF
Screen
Description
You enter the loop output options:
•
How the loop output is to be
scaled:
–
Analog
–
Digital
•
Analog scaling parameter:
–
Unipolar (default: 0 to 27648;
can edit)
–
Bipolar (default: -27648 to
24678; can edit)
–
Unipolar 20% offset (range:
5530 to 27648; is set and un-
changeable
•
Analog range parameter: Assign
the loop output range. The possible
range is -27648 to +27648, de-
pending on your scaling selection.
You can assign what conditions to
recognize with alarm inputs. Use the
checkboxes to enable the alarms as
required:
•
Low Alarm (PV): Set normalized
low alarm limit from 0.0 to high
alarm limit; default is 0.10.
•
High Alarm (PV): Set normalized
high alarm limit from low alarm limit
to 1.00; default is 0.90.
•
Analog Input Error: Assign where
the input module is attached to the
PLC.
Содержание SIMATIC S7-200
Страница 30: ...Product overview 1 7 Programming software S7 200 SMART 30 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 267: ...Program instructions 7 6 Counters S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 267 HSC modes 3 and 4 ...
Страница 394: ...Program instructions 7 18 Subroutine S7 200 SMART 394 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 425: ...Communication 8 5 PROFIBUS S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 425 ...
Страница 786: ...Technical specifications A 11 S7 200 SMART cables S7 200 SMART 786 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 798: ...Error codes C 4 PLC fatal error codes S7 200 SMART 798 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 848: ...Ordering information F 6 Human Machine Interface devices S7 200 SMART 848 System Manual V2 3 07 2017 A5E03822230 AF ...