Libraries
9.4 Open user communication library
S7-200 SMART
524
System Manual, V2.3, 07/2017, A5E03822230-AF
9.4.3
Open user communication library instruction error codes
The following table lists the Open User Communication (OUC) library (Page 498) instruction
error codes:
Error code
Description
C
O
N
N
E
C
T
S
E
N
D
R
E
C
V
D
I
S
C
O
N
N
E
C
T
0
No error
X
X
X
X
1
The data length input parameter is greater than the max-
imum allowed (1024 bytes).
X
X
2
The data buffer is not in I, Q, M, or V memory areas.
X
X
3
The data buffer does not fit in the memory area.
X
X
5
The connection is locked in another context. You are
attempting to access the same connection in both the
background (the Main) and in an interrupt program organ-
izational unit (POU) at the same time.
X
X
X
X
6
A UDP IP address or port error
X
7
An instance mismatch: The connection is busy with an-
other instance or the input data does not match the data
stored for the requested connection ID when the request
was initiated.
X
X
X
X
8
The Connection ID does not exist because the connection
has never been created, or the connection was terminat-
ed by your program using the DISCONNECT instruction.
X
X
X
X
9
A TCP_CONNECT, ISO_CONNECT, or UDP_CONNECT
instruction is in progress with this Connection ID.
X
X
X
10
A DISCONNECT instruction is in progress with this Con-
nection ID.
X
X
X
11
A TCP_SEND or UDP_SEND instruction is in progress
with this Connection ID.
X
X
12
A temporary communication error has occurred. The
connection cannot be started at this time. Try again.
X
X
X
13
The connection partner refused or actively dropped the
connection. The partner issued a disconnect to this CPU.
X
X
X
14
The CPU cannot reach the connection partner. There was
no answer to the connect request.
X
X
X
15
The CPU aborted the connection due to inconsistencies.
Disconnect and reconnect to correct the situation.
X
X
X
X
16
The Connection ID is already in use with a different IP
address, port, or TSAP combination.
X
Содержание SIMATIC S7-200
Страница 30: ...Product overview 1 7 Programming software S7 200 SMART 30 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 267: ...Program instructions 7 6 Counters S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 267 HSC modes 3 and 4 ...
Страница 394: ...Program instructions 7 18 Subroutine S7 200 SMART 394 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 425: ...Communication 8 5 PROFIBUS S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 425 ...
Страница 786: ...Technical specifications A 11 S7 200 SMART cables S7 200 SMART 786 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 798: ...Error codes C 4 PLC fatal error codes S7 200 SMART 798 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 848: ...Ordering information F 6 Human Machine Interface devices S7 200 SMART 848 System Manual V2 3 07 2017 A5E03822230 AF ...