PLC device configuration
6.1 Configuring the operation of the PLC system
S7-200 SMART
164
System Manual, V2.3, 07/2017, A5E03822230-AF
Operation of the Battery (BA01) Signal Board
The battery signal board contains a red LED that provides the customer a visual indication of
the battery health. An Illuminated LED indicates a battery low condition.
The CPU automatically utilizes the real-time clock on the signal board and performs the
battery test and battery health LED operation, whether or not the System block contains a
configuration for the signal board.
The battery signal board System block configuration contains selections that allow the
customer to report the battery low state as a diagnostic alarm and/or to report the battery
state (1=battery low, 0 = battery OK) in the LSB of the configured image register input byte
for the device (for example, I7.0). The customer must select the battery signal board in the
System block configuration in order to gain access to the additional battery health reporting
options.
6.1.16
Clearing PLC memory
To clear designated areas of PLC memory, follow these steps:
1.
Ensure that the PLC is in STOP mode.
2.
Click the Clear button from the Modify area of the PLC menu ribbon strip.
WARNING
Effect of clearing PLC memory on outputs
Clearing the PLC memory affects the state of digital and analog outputs. The default is
for digital and analog outputs to use a substitute value of 0. If you have defined
substitute values other than 0 or chosen "Freeze" for your digital or analog outputs, you
need to be aware that when you delete the system block, you are deleting the substitute
and freeze information and, as a result, your outputs shall return to the default value of
0. Furthermore, if you perform a selective clear such that you keep your system block
but delete your program block, then your analog outputs are frozen at their current
value. Until you download a new program block, the only way to make changes to the
state of the analog outputs is by means of the status chart.
If the S7-200 SMART PLC is connected to equipment when you clear the PLC memory,
changes to the state of the digital outputs can be transmitted to the equipment. If you
clear PLC memory without planning for the consequences to your digital and analog
outputs, your equipment could operate in an unpredictable fashion, which could result in
death or serious injury to personnel and/or damage to equipment.
Always follow appropriate safety precautions and ensure that your process is in a safe
state before clearing the PLC memory.
Содержание SIMATIC S7-200
Страница 30: ...Product overview 1 7 Programming software S7 200 SMART 30 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 267: ...Program instructions 7 6 Counters S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 267 HSC modes 3 and 4 ...
Страница 394: ...Program instructions 7 18 Subroutine S7 200 SMART 394 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 425: ...Communication 8 5 PROFIBUS S7 200 SMART System Manual V2 3 07 2017 A5E03822230 AF 425 ...
Страница 786: ...Technical specifications A 11 S7 200 SMART cables S7 200 SMART 786 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 798: ...Error codes C 4 PLC fatal error codes S7 200 SMART 798 System Manual V2 3 07 2017 A5E03822230 AF ...
Страница 848: ...Ordering information F 6 Human Machine Interface devices S7 200 SMART 848 System Manual V2 3 07 2017 A5E03822230 AF ...