Noise immunity, electromagnetic compatibility (EMC)
RFI suppression
Limit value class
To VDE 0871
A
Conducted interference on AC supply lines (230 V AC)
to IEC 801-4 (burst)
to IEC 801-5
between two lines (
µ
s pulses)
to IEC 801-5
between line and ground (
µ
s pulses)
2 kV
1 kV
2 kV
DC supply lines (24 V supply) to IEC 801-4 (burst)
1 kV
Signal lines (24 V DC) to IEC 801-4 (burst)
1 kV
Signal lines (230 V AC) to IEC 801-4 (burst)
2 kV
Immunity to discharge of static electricity to
IEC 801-2 (ESD)
Immunity of 4 kV contact discharge (8 kV air
discharge) is ensured with proper installation
(see Chapter 3).
Immunity to RF interference
RF field to IEC 801-6
limit value class 3 (up to 200 MHz),
corresponds to 3 V/m
Mechanical data
Mechanical requirements
Installation in stationary equipment, subject to
vibration; installation on ships and in vehicles if
special installation rules are observed, but not
on the engine.
Weight
approx. 14 kg
Dimensions (W x H x D)
482.6 x 432 x 310 mm
S5-135U/155U Central Controller
System Manual
4 - 16
C79000-B8576-C199-03