9.4
The 463 Analog Input Module
9.4.1
Design
The modules are designed as plug-in PCBs for central controllers and
expansion units with a backplane connector and with a blade
connector to accept a plug-in front connector. You can directly
connect the process signal lines to the front connector, which is
available separately, with screw or crimp terminals.
Addressing switch, mode
switches
Situated on each module is an addressing switch with six rockers to
set the module address. Analog input modules also have two switches
on the side with eight rockers for setting the mode, and receptacles for
range cards.
The modules are protected by covers on both sides.
9.4.2
Function of the Enable Input
The 463 module has an enable circuit. You can use the enable inputs
to switch off individual modules whilst the PLC is in operation. This
means that:
••
The module can no longer be addressed by the user program.
Modules which are switched off can be removed or inserted during
operation. If this is not necessary, operate the module with the enable
input switched off.
Blade Connector
Addressing Switch
Mode Switch
Front
Connector
Figure 9-12
Analog Input Module
9
The 463 Analog Input Module
System Manual
C79000-B8576-C109-03
9 - 37