Other faults
Other faults can be indicated by the green LEDs on the front plate
going off.
Indication
Possible Cause
Action
Green LEDs go
off and the
power supply
fails.
The Enable jumper is
out of place
Latching
Off-switching by
overvoltage at output
Internal fault in the
PSU
Check the jumper.
Switch the supply voltage
off and on again. If this
does not clear the fault,
there is an internal fault.
Send in the PSU for repair.