4.4.3
Fault Indications/
Fault Diagnostics
Load power supply faults are indicated by LEDs on the front plate:
IF...
THEN...
AND...
the red LED
lights up and
signalling
output H+ is at
logic 1,
there is a short-circuit
(overload) at outputs
2L+ to 5L+
the outputs will be
switched off. When the
short-circuit has been
corrected, 2L+ to 5L+
will return automatically
to normal operation.
the module
switches off (all
LEDs off),
output 1L+ was
overloaded with a
current of more than
5.5 A for a few seconds
when the overload has
been removed, the AC
supply must be briefly
switched off and on
again.
24 V/4 A Load Power Supply
System Manual
4 - 66
C79000-B8576-C199-03