System diagnostics
9.2 XML/PLC error messages
SIMATIC RF600
460
System Manual, 11/2018, J31069-D0171-U001-A21-7618
"ER"
LED
XML/
LED
(hex)
PLC block
(hex)
Error description
2 Hz
0x63
0xE6FE03
•
A parameter of an XML command has an invalid value or the parameter assignment of
the communications module or the reader was incorrect.
Possible causes / action to be taken:
–
Check the parameters in the Ident profile.
–
Check the relevant XML command.
–
Check the parameter assignment in HW Config / STEP 7 (TIA Portal).
–
The "WRITE-CONFIG" command has incorrect parameter settings.
–
After a startup, the reader or communications module has still not received an
"INIT".
•
The parameter assignment of the reader or communications module on
PROFIBUS/PROFINET was incorrect and the command cannot be executed.
Possible causes / action to be taken:
–
Length of the input/output areas is too small for the cyclic I/O word.
–
Check whether you have used the correct GSD file.
–
User data length set with the command (e.g. "READ") is too high.
•
Error when processing the command.
Possible causes / action to be taken:
–
The data in "AdvancedCmd" or "IID_CMD_STRUCT" is incorrect (e.g. "WRITE"
command with length = 0).
Check "AdvancedCmd" or "IID_CMD_STRUCT" and execute an "INIT".
–
The hardware of the reader/communications module is defective. The reader or
communications module receives bad data with an "INIT".
–
The AB byte does not match the user data length.
•
The wrong reset block was selected.
Possible causes / action to be taken:
–
Regardless of the selected reader system, use the "Reset_Reader" function block.
--
0x64
0xE6FE04 Presence error
A transponder has passed through the transmission window of a reader without being pro-
cessed.
•
This error message is not reported immediately. Instead, the reader or communications
module waits for the next write / read command. This command is replied to immediate-
ly with this error and the write/read command is not executed. The next command is ex-
ecuted normally again by the reader/communications module.
•
You can reset this error status using an "INIT".
•
Bit 2 is set in the "OPT1" parameter and there is no transponder in the transmission
window.