Approvals
CP 1242-7
82
Operating Instructions, 09/2011, C79000-G8976-C247-02
Industrial environments
The CP was developed for use in industrial environments.
Application
Requirements for emissions
Requirements for immunity
Industry
EN 61000-6-4:2007
EN 61000-6-2:2005
Electromagnetic compatibility (EMC)
The electromagnetic compatibility (EMC) of an electrical device is its capability of functioning
as intended in an electromagnetic environment without emitting electromagnetic interference
that could impair the operation of other electrical devices in the vicinity.
Electromagnetic compatibility - immunity
EN 61000-4-2
Electrostatic discharge
8 kV air discharge to all surfaces
4 kV contact discharge to exposed conductive surfaces
EN 61000-4-3
Radiated electromagnetic field
300 MHz to 2 GHz, 10 V/m, 80 % AM at 1 kHz
2.0 to 2.7 GHz, 3 V/m, 80 % AM at 1 kHz
EN 61000-4-4
Fast transient bursts
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to inputs/outputs
EN 61000-4-5
Surge immunity (power supply)
DC systems - 2 kV common mode, 1 kV push-pull
For DC systems (DC power supplies), external protection is necessary.
EN 61000-4-6
Conducted disturbances
150 kHz to 80 MHz, 10 V RMS, 80 % AM at 1 kHz
EN 61000-4-11
Voltage dips
DC systems
0 % for 1 cycle, 40 % for 12 cycles and 70 % for 30 cycles at 60 Hz
Electromagnetic compatibility - emission
Conducted emissions
EN 61000-6-4, Class A
Emitted radiation
EN 61000-6-4, Class A
Environmental conditions
Environmental conditions - transportation and storage
EN 60068-2-2, Test Bb, dry heat and
EN 60068-2-1 Test Ab, cold
-40°C to +70°C
EN 60068-2-30, Test Db, damp heat
25°C to 55°C, 95% humidity
EN 60068-2-14, Test Na, temperature shock
-40°C to +70°C, dwell time 3 hours, 2 cycles
EN 24180-2 Free fall
0.3 m in dispatch packaging
Atmospheric pressure
1 080 to 660 hPa (corresponding to an altitude of -1 000 to 3 500 m)