Displays and connectors
2.3 Electrical connections
CP 1242-7
22
Operating Instructions, 09/2011, C79000-G8976-C247-02
DIAG
(red / green)
-
Network
(red / green)
Connect
(green)
Signal
quality
(yellow /
green)
TeleService
(green)
Meaning
green
-
-
No connection to the telecontrol server
or
No configuration available
green
green
-
-
Connection to the telecontrol server
established
green
green
-
-
Data transfer
-
-
-
green
-
Good GSM network
(-73 ... > -53 dBm)
-
-
-
yellow
-
Medium strength GSM network
(-89 ... -75 dBm)
-
-
-
yellow
-
Weak GSM network
(-109 ... -91 dBm)
-
-
-
-
No GSM network
(< -111 dBm)
-
-
-
-
Currently no TeleService session
green
green
-
-
TeleService session running
1
green
-
-
-
Attempted login to TeleService session
1
When a TeleServiceconnection is being established, the LED is lit for at least 10 minutes.
2.3
Electrical connections
Power supply
The 3-pin socket for the external 24 V DC power supply is located on the top of the module.
The matching plug ships with the product.
You will find the pin assignment of the socket in section Pin assignment of the socket for the