Interrupts/diagnostic messages 

 

6.3 Diagnostic messages 

 

Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1) 

62

 

Manual, 08/2018, A5E41448857-AB 

Supply voltage outside the nominal range 

If the supply voltage L+ is outside the specified value range, the DIAG LED flashes and the 

module is passivated.  
When the voltage is then recovered (level must remain within the specified value for at least 

1 minute (see Technical specifications (Page 64): Voltages, Currents, Potentials)), the DIAG 

LED stops flashing. The module remains passivated. 

Generally applicable information on diagnostics 

Information on diagnostics that pertains to all fail-safe modules (for example, readout of 

diagnostics functions or passivation of channels) is available in the SIMATIC Safety – 

Configuring and Programming 

(

http://support.automation.siemens.com/WW/view/en/54110126

) manual. 

Содержание SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series

Страница 1: ..._________ SIMATIC ET 200SP Analog input module F AI 4xI 0 4 20mA 2 4 wire HF 6ES7136 6AA00 0CA1 Manual 08 2018 A5E41448857 AB Preface Documentation guide 1 Product overview 2 Connecting 3 Parameters address space 4 Applications of the F I O module 5 Interrupts diagnostic messages 6 Technical specifications 7 Response times A Representation of analog values B Original operating instructions ...

Страница 2: ...ly by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens prod...

Страница 3: ...rs to both the CPUs of the S7 1200 1500 automation system and CPUs of the ET 200SP distributed I O system STEP 7 In this documentation STEP 7 is used as a synonym for all versions of the configuration and programming software STEP 7 TIA Portal Note the following identified notes Note A note includes important information on the product described in the documentation on handling the product or on t...

Страница 4: ...tant issues in terms of operational safety You should subscribe to the corresponding notifications in order to obtain the latest information and to allow you to make any necessary modifications to your system Log on to Industry Online Support Follow the links below and click on Email on update on the right hand side in each case SIMATIC S7 300 S7 300F https support industry siemens com cs products...

Страница 5: ...nd components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures e g firewalls and or network segmentation are in place For additional information on industrial security measures that may be implemented please visit https www siemens com industrialsecurity Siemens products and solutions u...

Страница 6: ... 2 5 Tolerance window absolute 25 4 3 2 6 Tolerance window relative 26 4 3 2 7 Parameter assignment of discrepancy analysis for 1oo2 evaluation 27 4 3 2 8 Activated 34 4 3 2 9 Channel failure acknowledge 34 4 3 2 10 Measuring range 34 4 3 2 11 Diagnostics Wire break 35 4 3 2 12 Smoothing 35 4 4 Address space 38 5 Applications of the F I O module 40 5 1 Application 1 Safety mode SIL3 Cat 3 PLd with...

Страница 7: ... F AI 4xI 0 4 20mA 2 4 wire HF 6ES7136 6AA00 0CA1 Manual 08 2018 A5E41448857 AB 7 7 Technical specifications 64 7 1 Technical specifications 64 A Response times 69 B Representation of analog values 71 B 1 Representation of analog values 72 ...

Страница 8: ...access the specific content you require Basic information The system manual describes in detail the configuration installation wiring and commissioning of the SIMATIC ET 200SP distributed I O system The STEP 7 online help supports you in the configuration and programming Device information Product manuals contain a compact description of the module specific information such as properties wiring di...

Страница 9: ...I O system gathered together in one file You can find the Manual Collection on the Internet http support automation siemens com WW view en 84133942 mySupport With mySupport your personal workspace you make the most of your Industry Online Support In mySupport you can store filters favorites and tags request CAx data and put together your personal library in the Documentation area Furthermore your ...

Страница 10: ...e application examples support you with various tools and examples for solving your automation tasks Solutions are shown in interplay with multiple components in the system separated from the focus in individual products You can find the application examples on the Internet https support industry siemens com sc ww en sc 2054 TIA Selection Tool With the TIA Selection Tool you can select configure a...

Страница 11: ...nverted to UTC time to the module Program download to CPU Operating mode switchover RUN STOP Localization of the CPU by means of LED flashing Reading out CPU error information Reading the CPU diagnostic buffer Reset to factory settings Updating the firmware of the CPU and connected modules You can find the SIMATIC Automation Tool on the Internet https support industry siemens com cs ww en view 981...

Страница 12: ...an reserves This helps to prevent problems in commissioning or failures during productive operation even in advance of a planned operation This increases the availability of the production plant and helps improve operational safety The advantages at a glance Network optimization thanks to port specific calculation of the network load Increased production availability thanks to online scan and veri...

Страница 13: ...and name Function class LED for diagnostics Color coding module type 2D matrix code Function and firmware version Wiring diagram Color code for selecting the color identification labels LEDs for channel status BU type LED for supply voltage Article number Figure 2 1 View of the F AI 4xI 0 4 20mA 2 4 wire HF module Properties The module has the following technical properties Fail safe module PROFIs...

Страница 14: ... LED Diagnostics e g short circuit channel specific e g supply voltage missing module specific Channel and module wide passivation The module supports the following functions Firmware update I M identification data Value status WARNING The fail safe performance characteristics in the technical specifications apply for a mission time life of 20 years and a repair time of 100 hours If a repair withi...

Страница 15: ...e following accessories separately Labeling strips Color identification labels Reference identification label Shield connector Electronic coding element as spare part article number 6ES7193 6EF00 1AA0 You can find additional information about accessories in the Distributed I O System ET 200SP http support automation siemens com WW view en 58649293 System Manual ...

Страница 16: ...F AI 4xI 0 4 20mA 2 4 wire HF analog input module with the terminal assignment You can find additional information about wiring BaseUnits in the Distributed I O System ET 200SP http support automation siemens com WW view en 58649293 System Manual Block diagram The following figure shows the block diagram of the F AI 4xI 0 4 20mA 2 4 wire HF analog input module on the BaseUnit BU type A0 A1 ...

Страница 17: ...aseUnit Filter connection supply voltage available with light colored BaseUnit only DIAG Diagnostics LED green red In Current input positive channel n AI0 AI1 AI2 AI3 Channel status LED green In Current input negative channel n F0 F1 F2 F3 Channel fault LED red PWR Power LED green Figure 3 1 Block diagram Sensor supply WARNING Voltage dips and voltage fluctuations of the voltage supply are not buf...

Страница 18: ...gone Note Behavior of process values and diagnostics evaluation Sensor startup during module startup After the internal sensor supply is activated the evaluation of wire break and underflow diagnostics is suppressed for 3 seconds During this time the module makes the secure process data 0 available at all channels This suppresses a possible wire break or underflow diagnostics caused by the sensor ...

Страница 19: ...nal sensor supply When an external sensor supply is used other suitable measures are necessary to protect the input resistors e g external fast 50 mA fuse in the input circuit of the F module WARNING External sensor supply If you use an external sensor supply you need to take into consideration the voltage dips and voltage fluctuations when determining the safety function To ensure that the sensor...

Страница 20: ...he Appendix Representation of analog values Page 71 4 2 Parameters Parameters for F AI 4xI 0 4 20mA 2 4 wire HF WARNING Diagnostics functions should be activated or deactivated in accordance with the application see section Applications of the F I O module Page 40 The following parameters are possible Table 4 2 Configurable parameters Parameters Value range Default Parameter reas signment in RUN S...

Страница 21: ...d by F system No Module AI parameters Interference frequency sup pression 50 Hz 60 Hz 50 Hz No Module Channel parameters Channel n Sensor evaluation 1oo1 evaluation max SIL3 Cat 3 PLd 1oo2 evaluation max SIL3 Cat 4 PLe 1oo1 evaluation max SIL3 Cat 3 PLd No Channel Standard value MIN MAX MIN No Channel Discrepancy time 100 to 30000 ms 100 ms No Channel Tolerance window abso lute 2 0 to 20 0 5 0 No ...

Страница 22: ... 3 1 F parameters You must assign the PROFIsafe address F destination address together with F source address to the F module before you put it into operation You define the F source address using the Base for PROFIsafe addresses parameter in the F CPU An F destination address unique throughout the CPU is automatically assigned for each F module You can manually change the F destination addresses s...

Страница 23: ...2 evaluation max SIL3 Cat 4 PLe If you do not want to measure with a channel or channel pair disable the channel or the channel pair 1oo1 evaluation max SIL3 Cat 3 PLd With the 1oo1 evaluation there is one sensor and it is connected to the F module via a single channel 1oo2 evaluation max SIL3 Cat 4 PLe With the 1oo2 evaluation two input channels are occupied by Two single channel sensors One two ...

Страница 24: ...lue is outside the assigned tolerance window relative or absolute If the two redundant input channels of the channel pair differ by more than the specified tolerance and for longer than the specified discrepancy time but no longer than the duration of the maximum response time the F module detects a discrepancy error and triggers a diagnostic interrupt If the input channels fall below the specifie...

Страница 25: ...one decimal place If two redundant input channels of the channel pair differ by more than the tolerance specified here and for longer than the specified discrepancy time the F module detects a discrepancy error and triggers a diagnostic interrupt For more information regarding setting the tolerance window refer to Parameter assignment of discrepancy analysis for 1oo2 evaluation Page 27 Example You...

Страница 26: ... longer than the specified discrepancy time the F module detects a discrepancy error and triggers a diagnostic interrupt The two parameters Tolerance window absolute and Tolerance window relative are combined The Tolerance window absolute parameter is decisive in case of low process values For more information regarding setting the tolerance window refer to Parameter assignment of discrepancy anal...

Страница 27: ...screpancy analysis An assignable tolerance window is formed around the process value that represents the instantaneous standard value value that is signaled to the F CPU The tolerance window is formed relative to the process value or as an absolute value relative to the measuring range end value Relative and absolute tolerance windows are combined If the process value does not represent the standa...

Страница 28: ...o expiration of the discrepancy time input channels are no longer discrepant the discrepancy time is cleared and is restarted only when a new discrepancy is detected There is no valid old value after startup If the discrepancy is detected during this time 7FFFH is output for S7 300 400 F CPUs or 0 is output for S7 1200 1500 F CPUs and the discrepancy time is started If there is no longer a discrep...

Страница 29: ...0 for S7 1200 1500 F CPUs The discrepancy time is reset if the standard value lies within the tolerance window again In the PII the substitute value 0 is set for the safety program You calculate the maximum discrepancy time that is permitted in the respective application using the following formula Discrepancy time Maximum response time in case of discrepancy error 2 Conversion cycle time Smoothin...

Страница 30: ...ulate the maximum deviation of the current using the following formula With IME 20 mA full scale value IMA 0 mA for measuring range 0 20 mA start of scale value IMA 4 mA for measuring range 4 20 mA start of scale value Tabs Tolerance in ΔIabs Maximum deviation of current You can assign a value of 2 0 to 20 0 for the Tolerance window absolute parameter for each channel pair Figure 4 3 Absolute devi...

Страница 31: ...he standard value in this instant You can calculate the relative tolerance window using the following formula Calculate the maximum deviation of the current using the following formula With IEW Process standard value min max IMA 0 mA for measuring range 0 20 mA IMA 4 mA for measuring range 4 20 mA Trel Tolerance in ΔIrel Maximum deviation of current You can assign a value of 2 0 to 20 0 for the To...

Страница 32: ...bination of the Tolerance window absolute and Tolerance window relative parameters You can combine the Tolerance window absolute and Tolerance window relative parameters as needed The combined tolerance window shown in gray in the figure below is the maximum of Trel and Tabs T MAX Trel Tabs ΔI MAX ΔIrel ΔIabs With T Tolerance in ΔI Maximum deviation of current ...

Страница 33: ...andard value signaled to the F CPU In this example on the first occurrence of a discrepancy process value 1 is within the tolerance range again before expiration of the discrepancy time This means the discrepancy error is not signaled In this example on the second occurrence of a discrepancy process value 1 is outside the tolerance range when the discrepancy time expires As a result a discrepancy ...

Страница 34: ...te channel and the F parameter Reintegration after channel fault is set to Adjustable The value of this parameter specifies how the channel reacts after a channel fault Manual A channel failure is reintegrated after manual acknowledgment Automatically The channel is reintegrated automatically after a channel fault Manual acknowledgment is not necessary Use in S7 300 400 F CPUs The value of this pa...

Страница 35: ...terrupt in the F CPU With an assigned measuring range of 0 to 20 mA the wire break diagnostics is permanently set by default With currents 0 4442 mA a wire break is detected and a diagnostic interrupt is triggered in the F CPU If you do not need a channel deactivate the channel Then a wire break is not detected 4 3 2 12 Smoothing Using smoothing Smoothing of analog values provides a stabilized ana...

Страница 36: ...g a unit step You can find an example below Note Smoothing is reset after startup short circuit wire break or another channel fault If for example smoothing with 16 conversion cycles is assigned and all channels are active it takes up to 2000 ms until the process value is signaled with a configured interference frequency suppression of 50 Hz Until the first valid process value the F module signals...

Страница 37: ...ion cycle time Smoothing Discrepancy time 2 Conversion cycle time Example One channel pair connected and configured activated interference frequency 50 Hz smoothing 16 conversion cycles discrepancy time 2000 ms conversion cycle time calculated with the formula from section Response times Page 69 Max response time in case of discrepancy error 2 70 ms 16 2000 ms 2 70 ms 4380 ms If a discrepancy exis...

Страница 38: ...a occupy the following addresses in the analog input module F AI 4xI 0 4 20mA 2 4 wire HF out of all the assigned addresses in the F CPU Table 4 4 User data address assignment in the input range Byte in the F CPU Assigned bits in F CPU per F module 7 6 5 4 3 2 1 0 IB x 0 Input value at channel 0 Result of the 1oo2 evaluation channel 0 2 IB x 1 IB x 2 Input value at channel 1 Result of the 1oo2 eva...

Страница 39: ... AI 4xI 0 4 20mA 2 4 wire HF 6ES7136 6AA00 0CA1 Manual 08 2018 A5E41448857 AB 39 Additional information For detailed information about F I O access refer to the SIMATIC Safety Configuring and Programming http support automation siemens com WW view en 54110126 manual ...

Страница 40: ...ng section in the Distributed I O System ET 200SP http support automation siemens com WW view en 58649293 System Manual 5 1 Application 1 Safety mode SIL3 Cat 3 PLd with 2 wire transducer Introduction Below you will find the wiring scheme and the parameter assignment of the F AI 4xI 0 4 20mA 2 4 wire HF for Application 1 Safety mode SIL3 Cat 3 PLd 1oo1 1v1 evaluation Possible diagnostic messages t...

Страница 41: ...20mA 2 4 wire HF 6ES7136 6AA00 0CA1 Manual 08 2018 A5E41448857 AB 41 Current measurement 0 4 to 20 mA 2 wire transducer Four process signals can be connected to the F module in this interconnection variant Sensor supply UV is provided by the F module for 4 channels You can also supply the sensors by means of an external sensor supply ...

Страница 42: ...0 optional P1 P2 AUX Internal self assembling voltage buses Connection to left dark colored BaseUnit Connection to left interrupted light colored BaseUnit Filter connection supply voltage available with light colored BaseUnit only DIAG Diagnostics LED green red External fuse AI0 AI1 AI2 AI3 Channel status LED green In Current input positive channel n F0 F1 F2 F3 LED channel fault red In Current in...

Страница 43: ...1 Table 5 1 Parameters for application 1 of F AI 4xI 0 4 20mA 2 4 wire HF Parameters Range of values in safety mode Behavior after channel faults Passivate the entire F module Passivate channel Interference frequency suppression 50 Hz 60 Hz Sensor evaluation 1oo1 evaluation max SIL3 Cat 3 PLd Measuring range 0 20 mA 4 20 mA Diagnostics Wire break in the measuring range 4 to 20 mA Disable Enable Sm...

Страница 44: ...and the parameter assignment of the F AI 4xI 0 4 20mA 2 4 wire HF for application 2 Safety mode SIL3 Cat 4 PLe 1oo2 2v2 evaluation Possible diagnostic messages the error causes and possible corrective measures are given in section Diagnostic messages Page 58 Current measurement 0 4 to 20 mA 2 wire transducer Two process signals can be connected to the F module in this interconnection variant Senso...

Страница 45: ...Internal self assembling voltage buses Connection to left dark colored BaseUnit Connection to left interrupted light colored BaseUnit Filter connection supply voltage available with light colored BaseUnit only DIAG Diagnostics LED green red External fuse AI0 AI1 AI2 AI3 Channel status LED green In Current input positive channel n F0 F1 F2 F3 LED channel fault red In Current input negative channel ...

Страница 46: ...e HF Parameters Range of values in safety mode Standard value MIN MAX Discrepancy time 100 to 30000 ms Tolerance window absolute 2 0 to 20 0 Tolerance window relative 2 0 to 20 0 Behavior after channel faults Passivate the entire F module Passivate channel Interference frequency suppression 50 Hz 60 Hz Sensor evaluation 1oo2 evaluation max SIL3 Cat 4 PLe Measuring range 0 to 20 mA 4 to 20 mA Diagn...

Страница 47: ...nd the parameter assignment of the F AI 4xI 0 4 20mA 2 4 wire HF for Application 3 Safety mode SIL3 Cat 3 PLd 1oo1 1v1 evaluation Possible diagnostic messages the error causes and possible corrective measures are given in section Diagnostic messages Page 58 Current measurement 0 4 to 20 mA 4 wire transducer Four process signals can be connected to the F module in this interconnection variant Senso...

Страница 48: ...d label with color code CC00 optional P1 P2 AUX Internal self assembling voltage buses Connection to left dark colored BaseUnit Connection to left interrupted light colored BaseUnit Filter connection supply voltage available with light colored BaseUnit only DIAG Diagnostics LED green red External fuse AI0 AI1 AI2 AI3 Channel status LED green In Current input positive channel n F0 F1 F2 F3 LED chan...

Страница 49: ...able 5 3 Parameters for application 3 of F AI 4xI 0 4 20mA 2 4 wire HF Parameters Range of values in safety mode Behavior after channel faults Passivate the entire F module Passivate channel Interference frequency suppression 50 Hz 60 Hz Sensor evaluation 1oo1 evaluation max SIL3 Cat 3 PLd Measuring range 0 to 20 mA 4 to 20 mA Diagnostics Wire break in the measuring range 4 to 20 mA Disable Enable...

Страница 50: ... and the parameter assignment of the F AI 4xI 0 4 20mA 2 4 wire for application 4 Safety mode SIL3 Cat 4 PLe 1oo2 2v2 evaluation Possible diagnostic messages the error causes and possible corrective measures are given in section Diagnostic messages Page 58 Current measurement 0 4 to 20 mA 4 wire transducer Two process signals can be connected to the F module in this interconnection variant Sensor ...

Страница 51: ...ed label with color code CC00 optional P1 P2 AUX Internal self assembling voltage buses Connection to left dark colored BaseUnit Connection to left interrupted light colored BaseUnit Filter connection supply voltage available with light colored BaseUnit only DIAG Diagnostics LED green red External fuse AI0 AI1 AI2 AI3 Channel status LED green In Current input positive channel n F0 F1 F2 F3 LED cha...

Страница 52: ...e HF Parameters Range of values in safety mode Standard value MIN MAX Discrepancy time 100 to 30000 ms Tolerance window absolute 2 0 to 20 0 Tolerance window relative 2 0 to 20 0 Behavior after channel faults Passivate the entire F module Passivate channel Interference frequency suppression 50 Hz 60 Hz Sensor evaluation 1oo2 evaluation max SIL3 Cat 4 PLe Measuring range 0 to 20 mA 4 to 20 mA Diagn...

Страница 53: ... DIAG green red Channel status green Channel fault red PWR green Figure 6 1 LED display Meaning of the LED displays The following tables show the meaning of the status and error displays Remedies for diagnostics alarms can be found in section Diagnostic messages Page 58 WARNING The DIAG LED and the channel status and channel fault LEDs of the outputs are not designed as safety related LEDs and the...

Страница 54: ...n S7 1200 1500 F CPUs At least one channel is waiting for a user acknowledgment Flashing Operation in S7 1200 1500 F CPUs The F module is waiting for a user ac knowledgment after a module fault Operation in S7 300 400 F CPUs The F module is waiting for a user acknowl edgment Channel status channel fault LED Table 6 2 Status display of the LEDs channel status channel error Channel status Channel fa...

Страница 55: ... 6 3 Status display of the LEDs channel status DIAG channel error Channel status DIAG Channel fault Meaning Off Flash ing All On The PROFIsafe address does not match the configured PROFIs afe address Flashing Flash ing Off Identification of the F module when assigning the PROFIsafe ad dress PWR LED Table 6 4 Status display of LED PWR PWR Meaning Off Supply voltage L missing On Supply voltage L ava...

Страница 56: ...e fault and validate your safety function Follow the fault remedying procedure described in section Diagnostic messages Page 58 Scope of diagnostic interrupt F module Overtemperature Parameter error Supply voltage missing Channel component temporarily not available Mismatch of safety destination address F_Dest_Add Safety destination address not valid F_Dest_Add Safety source address not valid F_So...

Страница 57: ...ailable Scope of diagnostic interrupt Channel Diagnostics Wire break can only be configured for measuring range 4 20mA High limit exceeded Low limit violated Safety related switch off Internal supply voltage of the module failed Common mode error Analog input signal not recorded unique Internal sensor supply short circuit to P Overload or internal sensor supply short circuit to M Discrepancy error...

Страница 58: ...age 64 Once the temperature has been re duced and returns to the specified range the F module must be removed and inserted or the power switched OFF and ON Wire break 6H Possible causes A cable to the sensor is broken Fault at the external circuit Defective sensor Wrong sensor type set in the parame ters Input channel not used Measurement resistance too high Check the possible causes and elimi nat...

Страница 59: ...eds SIL from specific device application 44H The F module detected a discrepancy between the SIL setting of the communi cation and the application Parameter F_CRC_Length does not match the generat ed values 45H The F module detected a discrepancy in the CRC length Version of F parameter set incorrectly 46H The F module detected an incorrect F_Par_Version or an invalid F_Block_ID CRC1 fault 47H The...

Страница 60: ...tween two input channels is too high Correct the input wiring Invalid inconsistent firmware present 11BH The firmware is incomplete and or firm ware added to the F module is incompat ible This leads to errors or functional limitations when operating the F module Perform a firmware update for the F module Note any error messag es Use only firmware versions re leased for this F module Diagnostics me...

Страница 61: ...ture 312H The minimum permissible temperature limit has been violated Operate the F module within the speci fied temperature range see Technical specifications Page 64 Discrepancy error 314H The discrepancy time set for 1oo2 opera tion has been exceeded Possible causes of the discrepancy error Incorrect parameter assignment Wire break in the sensor s supply cable Check the discrepancy time the sen...

Страница 62: ...age is then recovered level must remain within the specified value for at least 1 minute see Technical specifications Page 64 Voltages Currents Potentials the DIAG LED stops flashing The module remains passivated Generally applicable information on diagnostics Information on diagnostics that pertains to all fail safe modules for example readout of diagnostics functions or passivation of channels i...

Страница 63: ...A valid process value is output for the channel 0B A fail safe value is output for the channel or the channel is deactivated Note You may only access the addresses occupied by user data and value status The other address areas occupied by the F modules are assigned for functions including safety related communication between the F modules and F CPU in accordance with PROFIsafe 1oo2 evaluation of t...

Страница 64: ...duct function I M data Yes I M0 to I M3 Engineering with STEP 7 TIA Portal configurable integrated as of version V15 with HSP 203 CiR Configuration in RUN Reparameterization possible in RUN No Calibration possible in RUN No Supply voltage Rated value DC 24 V permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Input current Current consump...

Страница 65: ... rated values currents 0 to 20 mA Yes Input resistance 0 to 20 mA 125 Ω 4 mA to 20 mA Yes Input resistance 4 mA to 20 mA 125 Ω Cable length shielded max 1 000 m Analog value generation for the inputs Measurement principle Sigma Delta Integration and conversion time resolution per channel Resolution with overrange bit including sign max 16 bit Integration time parameterizable Yes Integration time m...

Страница 66: ...nput range 2 Basic error limit operational limit at 25 C Current relative to input range 0 1 Interference voltage suppression for f n x f1 1 f1 interference frequency Series mode interference peak value of interfer ence rated value of input range min 40 dB Common mode interference min 70 dB Interrupts diagnostics status information Diagnostics function Yes Alarms diagnostic messages section in the...

Страница 67: ...de Performance level according to ISO 13849 1 PLe Category according to ISO 13849 1 Cat 4 SIL acc to IEC 61508 SIL 3 Probability of failure for service life of 20 years and repair time of 100 hours Low demand mode PFDavg in accordance with SIL3 5 00E 05 High demand continuous mode PFH in ac cordance with SIL3 1 00E 09 1 h Ambient conditions Ambient temperature during operation horizontal installat...

Страница 68: ...l 08 2018 A5E41448857 AB Temperature characteristic values Note When the ambient temperature exceeds 55 C you must only apply a maximum total current of 3 A to an adjacent F DQ 4x24VDC 2A PM HF Dimension drawing See ET 200SP BaseUnits manual See also ET 200SP BaseUnits http support automation siemens com WW view en 58532597 133300 ...

Страница 69: ...x acknowledgment time Device Acknowledgment Time TDAT 20 ms Basic response time 20 ms Response time per channel At 50 Hz 25 ms At 60 Hz 22 ms Conversion cycle time basic response time N response time per channel N number of active channels The conversion cycle time is the time in which all activated channels are processed converted once Typical response time You can calculate the typical response ...

Страница 70: ...rsion cycle time Smoothing Discrepancy time Conversion cycle time Maximum response time 2 Conversion cycle time Smoothing Discrepancy time 2 Conversion cycle time According to the following formula if a channel fault is present Typical response time Conversion cycle time Max response time 2 Conversion cycle time This means that for OFDT the time on occurrence of a discrepancy error should be taken...

Страница 71: ...uring ranges that you can use with the F AI 4xI 0 4 20mA 2 4 wire HF analog input module Measured value resolution The analog values are shown as fixed point number in two s complement The resolutions shown here are 16 bits including sign Table B 1 Resolution of the analog values Resolution in bits Values Analog value Decimal Hexadecimal High byte Low byte 16 1 1H Sign 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ...

Страница 72: ...anges Table B 2 Current measuring range 0 to 20 mA Values Current measuring range Range Dec Hex 0 to 20 mA 32512 7F00H 23 518 mA Overflow2 32511 27649 7EFFH 6C01H 23 518 mA 20 0007 mA Overrange 27648 614 6C00H 266H 20 mA 0 4442 mA Nominal range 613 1 0 265H 1H 0H 0 4442 mA 723 4 nA 0 mA Wire break1 1 The F module signals a wire break 7FFFH for S7 300 400 F CPUs or 0 for S7 1200 1500 F CPUs 2 In ST...

Страница 73: ...A Overflow2 Overflow2 32511 27649 7EFFH 6C01H 22 814 mA 20 0006 mA Overrange Overrange 27648 1 0 6C00H 1H 0H 20 mA 4 mA 578 7 nA 4 mA Nominal range Nominal range 1 691 FFFFH FD4DH 3 9994 mA 3 6 mA Underrange Underrange 692 6144 FD4CH E800H 3 6 mA 0 4444 mA Wire break1 6145 E7FFH 0 4444 mA Underflow2 1 The F module signals a wire break 7FFFH for S7 300 400 F CPUs or 0 for S7 1200 1500 F CPUs 2 In S...

Отзывы: