![Siemens SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/siemens/simatic-et-200sp-f-ai-4xi-0-4-20ma-2-4-wire-hf-series/simatic-et-200sp-f-ai-4xi-0-4-20ma-2-4-wire-hf-series_manual_1265347046.webp)
Applications of the F-I/O module
5.2 Application 2: Safety mode SIL3/Cat.4/PLe with 2-wire transducer
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
46
Manual, 08/2018, A5E41448857-AB
Assignable parameters for application 2
Table 5- 2
Parameters for application 2 of F-AI 4xI 0(4)..20mA 2-/4-wire HF
Parameters
Range of values in safety mode
Standard value
•
MIN
•
MAX
Discrepancy time
100 to 30000 ms
Tolerance window %, absolute
2.0 to 20.0%
Tolerance window %, relative
2.0 to 20.0%
Behavior after channel faults
•
Passivate the entire F-module
•
Passivate channel
Interference frequency suppression
•
50 Hz
•
60 Hz
Sensor evaluation
1oo2 evaluation (max. SIL3/Cat.4/PLe)
Measuring range
•
0 to 20 mA
•
4 to 20 mA
Diagnostics: Wire break
(in the measuring range 4 to 20 mA)
•
Disable
•
Enable
Smoothing
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles