![Siemens SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series Скачать руководство пользователя страница 55](http://html.mh-extra.com/html/siemens/simatic-et-200sp-f-ai-4xi-0-4-20ma-2-4-wire-hf-series/simatic-et-200sp-f-ai-4xi-0-4-20ma-2-4-wire-hf-series_manual_1265347055.webp)
Interrupts/diagnostic messages
6.1 Status and error display
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Manual, 08/2018, A5E41448857-AB
55
Channel status/DIAG/channel fault LED
Table 6- 3
Status display of the LEDs channel status / DIAG / channel error
Channel
status
DIAG
Channel
fault
Meaning
Off
Flash-
ing
All On
The PROFIsafe address does not match the configured PROFIs-
afe address.
Flashing
Flash-
ing
Off
Identification of the F-module when assigning the PROFIsafe ad-
dress.
PWR LED
Table 6- 4
Status display of LED PWR
PWR
Meaning
Off
Supply voltage L+ missing
On
Supply voltage L+ available