Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
20
Manual, 08/2018, A5E41448857-AB
Parameters/address space
4
4.1
Measurement types and measuring ranges
The following table shows the measurement types and the respective measuring range.
Table 4- 1
Measurement types and measuring ranges
Measurement
type
Measuring range
Resolution
Current
0 to 20 mA (2-wire and 4-wire transducer)
4 to 20 mA (2-wire and 4-wire transducer)
16 bits including sign
16 bits including sign
You can find the tables of the measuring ranges as well as overflow, overrange, etc. in the
Appendix Representation of analog values (Page 71).
4.2
Parameters
Parameters for F-AI 4xI 0(4)..20mA 2-/4-wire HF
WARNING
Diagnostics functions should be activated or deactivated in accordance with the application,
see section Applications of the F-I/O module (Page 40).
The following parameters are possible:
Table 4- 2
Configurable parameters
Parameters
Value range
Default
Parameter reas-
signment in RUN
Scope
F-parameters:
Manual assignment of the F-
monitoring time
•
Disable
•
Enable
Disable
No
Module
F-monitoring time
1 to 65535 ms
150 ms
No
Module
F-source address
1 to 65534
depends on parame-
ter assignment of F-
CPU
No
Module
F-destination address
1 to 65534
suggested by F-
system
No
Module
F-parameter signature (with-
out address)
0 to 65535
calculated by F-
system
No
Module